Friedrich R-410A service manual Troubleshooting, Defective switch On-Off

Models: R-410A

1 32
Download 32 pages 56.71 Kb
Page 27
Image 27
Defective switch (On-Off)

TROUBLESHOOTING

PROBLEM

POSSIBLE CAUSE

POSSIBLE SOLUTION

 

 

 

 

Defective switch (On-Off)

Check continuity across terminals 2 and 3.

 

 

 

 

Fan capacitor open.

Test with capacitor analyzer. Replace if bad.

 

 

 

 

Inoperative fan motor.

Check power and if okay, perform continuity test.

 

Replace if bad.

 

 

Fan motor does

 

 

Incorrect wiring of fan circuit.

Connect per wiring diagram.

not run.

 

 

Solid state relay open.

Replace relay.

 

 

 

 

 

Seized motor bearings.

Replace motor.

 

 

 

 

Bound fan blade or blower wheel.

Adjust for proper clearance.

 

 

 

 

 

 

PROBLEM

POSSIBLE CAUSE

POSSIBLE SOLUTION

 

 

 

Switch (On-Off)

Defective (On-Off) switch or

 

does not cut fan

Replace switch or relay.

defective relay.

motor off.

 

 

 

 

 

 

 

 

 

PROBLEM

POSSIBLE CAUSE

 

 

 

 

 

Poor installation.

Refer to installation instructions for proper

 

installation.

 

 

 

 

 

 

Fan blade striking chassis or

Adjust fan blade or blower wheel clearance.

 

blower wheel housing.

 

 

Noisy and/or

 

 

 

Check for deteriorated compressor grommets.

vibration.

Compressor vibrating.

Replace as needed.

 

 

 

 

 

 

Loose cabinet parts, improperly

 

 

mounted components, tubing

Adjust and tighten as required.

 

rubbing.

 

 

 

 

 

 

 

PROBLEM

POSSIBLE CAUSE

POSSIBLE SOLUTION

 

 

 

 

Evaporator drain pan overflowing.

Clean obstructed drain trough.

 

 

 

Water leaks into

Condensation forming on bottom of

Evaporator drain pan broken or cracked. Replace

base pan.

chassis seal gasket missing or defective.

room.

 

 

Water dripping from discharge air

Dirty evaporator coil, or extremely high humidity

 

 

grilles.

conditions. Clean coil or check application.

 

 

 

 

 

 

PROBLEM

POSSIBLE CAUSE

POSSIBLE SOLUTION

 

 

 

 

 

 

 

Extremely high humid conditions.

Install 01900-235 drain kit.

 

 

 

 

Water in center section of base pan

Drain trough. Check level. Ensure 1/4” tilt toward

Excessive water

(compressor area).

rear.

leaks outside.

Dirty condenser coil.

Clean with steam or detergent.

 

 

 

 

Fan blade and slinger ring

Adjust fan blade to 1/2” clearance from condenser

 

improperly positioned.

coil.

 

 

 

26

Page 27
Image 27
Friedrich R-410A service manual Troubleshooting, Defective switch On-Off