Sterling Power Products 30F to 65F Problem, Cause, Solution, Pump runs, compressor

Models: 30F to 65F

1 43
Download 43 pages 9.99 Kb
Page 38
Image 38
Manual background

Problem

Cause

Solution

Pump runs, compressor

Refrigerant is low.

Check the refrigerant

will not.

charge.

 

 

 

Sight glass should be clear

 

Pressure switch contacts

while compressor runs.

 

are open.

Call for service if bubbling

 

 

or foaming

 

Refrigerant high pressure

Check for dirty condenser.

 

cutout switch contacts are

Check for condenser air

 

open.

obstruction.

 

Defective fan motor.

Repair or replace.

 

 

Check for high/low voltage.

 

Compressor internal

Must be within plus or

 

minus 10% of the

 

overload is open. Allow

 

nameplate rating. Check

 

time to cool and reset.

 

for poor compressor

 

 

 

 

electrical connections.

 

Broken wire in the

Locate and repair.

 

compressor control circuit.

 

 

Unit runs continuously, but

Restricted condenser

Clean the condenser.

not enough cooling power.

airflow.

 

 

Unit low on refrigerant.

Call Service.

 

Inefficient compressor.

Call Service.

 

Unit undersized for

Call Sales Representative.

 

application.

 

 

Page 38

SMC Series Chillers

Page 38
Image 38
Sterling Power Products 30F to 65F installation manual Problem, Cause, Solution, Pump runs, compressor