RMT LED
The orange RMT LED is lit during remote operation.
AT LED
The orange AT LED flashes during
SUB1 LED
The orange SUB1 LED energizes whenever the process temperature is two degrees (2°F/ºC) or more below the To Process set point. The compressor then shuts down by means of a latching circuit, and does not run again until the temperature at the To Process thermocouple is two degrees (2°F/ºC) above the set point.
This +2°F/ºC control set point is
5-4 Temperature Controller Keys
AT AT Key
Press and hold the AT AT key for two seconds to initiate or stop the
Display Key
The functions of the Display key change, based on how long you press it. Press the Display key for less than one (1) second to scroll through parameters within the mode.
Press the Display key for at least one (1) second or more to display the menu; this function also lets you select the mode you need to adjust.