8 | Troubleshooting Guide | ||
|
|
|
|
|
|
|
|
Problem | Cause | Solution |
|
Chiller will not run. |
| Check main disconnect |
|
| No power. | fuses, wiring, and power |
|
|
| lead to the unit. |
|
| Wrong voltage supplied to | Voltage must be within plus |
|
| or minus 10% of the |
| |
| the chiller. |
| |
| nameplate rating. |
| |
|
|
| |
| Defective on/off switch. | Replace. |
|
| Control circuit fuse blown. | Replace, check the |
|
| transformer. |
| |
|
|
| |
| Defective control | Replace. |
|
| transformer. |
| |
|
|
| |
Pump runs, compressor | No process load on the | Increase the process load. |
|
cycles at short intervals. | chiller. |
| |
|
| ||
| Refrigerant is low. | Check the refrigerant |
|
| charge. |
| |
|
|
| |
The leaving water | Refrigerant is low. | Check the refrigerant |
|
temperature is too high. | charge. |
| |
|
| ||
|
| Make sure that the coolant |
|
|
| solution is right for the |
|
| Improper water/glycol | process — must be 75% |
|
| solution. | water and 25% glycol. |
|
|
| See Figure 6 on page 16 |
|
|
| for more information. |
|
Pump pressure is low (see | Check for foreign matter. | Clean the system. |
|
pump curves). |
| ||
|
|
| |
Pump pressure is too high. |
| Check for partially closed |
|
| Restricted water flow. | valves, etc. Be sure all |
|
|
| lines are properly sized. |
|