Optional Graphic Panel

6

Optional Graphic Panel

 

 

6-1 Indicator Lights

6-1 Indicator Lights PUMP ON (green)

This indicator lights when the pump is running.

 PUMP ON (green) COMPRESSOR ON (green) COMPRESSOR ON (green)

This indicator lights when the compressor is operating.

 HIGH REFRIGERANT PRESSURE (red) LOW REFRIGERANT PRESSURE (red) LOW WATER FLOW (red), PCA units without pump only6-2 SwitchesPOWERManual background HIGH REFRIGERANT PRESSURE (red)

This indicator lights if the condensing pressure exceeds a safe level. The chiller goes to Idle mode until the high refrigerant pressure cutout resets. The light then goes out and the chiller automatically restarts. Call a qualified refrigeration service technician for service.

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background LOW REFRIGERANT PRESSURE (red)

This indicator lights if the refrigerant pressure drops below a safe level. The compressor will stop and remain off until the pressure reaches a safe level. The light will go out and the chiller will then resume operation automatically.

Manual backgroundManual backgroundManual background LOW WATER FLOW (red), PCA units without pump only

This indicator lights if the flow switch senses chilled water/glycol flow through the evaporator dropping to an unacceptable level. The compressor will stop until the flow switch senses adequate flow and restarts the chiller.

6-2 Switches

POWER

This switch energizes the control circuit and also turns off the chiller.