Friedrich RT5 manual Configuration Mode, Configuration Mode Settings

Models: RT5

1 14
Download 14 pages 32.96 Kb
Page 8
Image 8
Configuration Mode

Configuration Mode

The configuration mode is used to set the RT5 to match your heating/cooling system. The RT5 functions with Friedrich PTAC models.

Ensure that the thermostat is configured for air conditioning with ELECTRIC HEAT ONLY.

To configure the RT5, perform the following steps:

1.Remove the cover of the thermostat by gently pulling on one of the corners.

2.Simultaneously hold the SW5 and SW6 buttons in for 5 seconds while the RT5 is in OFF mode.

3.Press the Configuration Mode Settings or Manual background button to change settings within each screen.

4.Press the SW6 button to advance to the next screen.

Manual backgroundManual background Note: The SW5 button will return you to the previous screen.

5.To exit configuration mode, slide the Mode switch to Heat or Cool.

Configuration Mode Settings

The nine (9) setup screens for Configuration Mode are as follows:

1.Heat pump and Non Heat Pump – Press the Manual background or Manual background button to configure as heat pump, or non-heat pump system. For heat pumps, there will be an anti-short cycle delay for heating and cooling

• 0 = Non-heat pump system

Press the SW6 button to advance to the next screen.

2.Temperature Scale (F or C) – Choose Fahrenheit or Celsius. Press the Manual background or Manual background button to select.

Press the SW6 button to advance to the next screen.

SET

REMOTE

 

ROOM

 

DIFF

 

FILTER

 

SET

REMOTE

 

ROOM

 

DIFF

 

FILTER

 

6

Page 8
Image 8
Friedrich RT5 manual Configuration Mode, Configuration Mode Settings