Friedrich SP05A10 3-2Function Description, 3-2-1Cooling operation mode, 3-2-2Fan operation mode

Models: SP05A10

1 28
Download 28 pages 19.6 Kb
Page 7
Image 7
3-2 Function Description

3-2 Function Description

3-2-1 Cooling operation mode

The compressor is turned on and off according to the ambient temperature and set temperature.

1)Compressor on and off control

Compressor on and off control according to the ambient temperature

*The compressor is turned off when "ambient temperature = set temperature

*The compressor is turned on when "ambient temperature = set temperature +1˚C"

2)Default value after power reset set temperature = 75˚F

Fan speed = High

3) Set temperature indicating (setting) range : 1˚F interval from 64˚F to 86˚F.

3-2-2 Fan operation mode

1)If "Fan operation mode" signal is received from remocon or panel.

the compressor is immediately turned off and only fan motor is operated at set blowing speed.

it changes such as "High Med Low High"( if Fan speed is selected).

2)The initial Fan motor speed is set to "High".

3)The set temperature can not be indicated and set.

3-2-3 Energy saver operation mode

*If the compressor turn off at the cooling operation, the fan motor turn off after operation during the fixation time only, and operation that energy saver by turn off the fixation time only, and operation that energy saver by turn off the motor continuously before the condition of the compressor on.

*The fan motor is not operated at flow wind operation.

*Energy saver operation specification at the cooling operation.

1)Fan motor control in compressor on : operate with setting wind speed

2)Fan motor control in compressor off : After compressor off, the fan motor is operated breeze for 2 minutes and then it turn off.

3)After the fan motor off, the compressor and fan motor is operated normally when the compressor on.

3-2

FRIEDRICH AIR CONDITIONING CO.

Page 7
Image 7
Friedrich SP05A10 service manual 3-2Function Description, 3-2-1Cooling operation mode, 3-2-2Fan operation mode