3. INSTALLATION
3.1 HOW TO INSTALL THE UNIT
1.To avoid vibration and noise, make sure the unit is installed securely and firmly.
2.Install the unit where the sunlight does not shine directly on the unit.
If the unit receives direct sunlight, build an awning to shade the cabinet.
3.There should be no obstacle, like a fence, within 20" which might restrict heat radiation from the condenser.
4.To prevent reducing performance, install the unit so that louvers of the cabinet are not blocked.
5.Install the unit a little obliquely outward not to leak the condensed water into the room (about 1/4").
6.Install the unit with its bottom portion 30~60" above the floor level.
7.Stuff the foam between the top of the unit and the wall to prevent air and insects from getting into the room.
8.The power cord must be connected to an independent circuit. The green wire must be grounded.
9.Connect the drain tube to the base pan hole in the rear side if you need to drain (consult a dealer).
Plastic hose or equivalent may be connected to the drain tube.
Cooled air
30"~60"
Figure 19
AwningFence
Heat radiation
About 1/4"
Over 20"
3.2 CHECKING INSTALLATION
The setting conditions must be checked prior to initial starting.
The items mentioned below are especially important checking points when the installation is finished.
1.Grounding wire (Green or Green and Yellow) is provided in the power cord. The green wire must be grounded.
2.Connect to a
3.To avoid vibration or noise, make sure the air conditioner is installed securely.
4 Avoid placing furniture or draperies in front of the air inlet and outlet.
3.3.HOW TO DRAIN (When using drain pipe)
The air conditioner must be installed horizontally or tilted slightly to the outside for proper water drainage.
On exceptionally hot and humid days the air conditioner may overflow condensed water. If the air conditioner is used in hot and a high humidity zone, exchange the DRAIN CAP for the
DRAIN PIPE.(See Figure 20, Figure 21)
BASE PAN
Figure 20
1
BASE PAN
2
Figure 21
BOTTOM
DRAIN CAP
BOTTOM
DRAIN PIPE