PROCEDURE C CONTINUED

PROCEDURE C CONTINUED

7

To achieve rearward slope for unit draining,

remove the backing from the 1113/16" shim

 

 

strips and attach them as shown below in Fig.

23.The higher portion of shim is to be placed in front of the rib on the base of wall sleeve.

 

 

 

 

 

 

 

1" high

 

 

 

 

 

3/4" High

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIG. 22

CAUTION

Air conditioners covered in this manual pose an excessive weight hazard. Two or more people are needed to move and install the unit.

To prevent injury or strain, use proper lifting and carrying techniques when moving unit.

When handling the air conditioner, be careful to avoid cuts from sharp metal fins on front and rear coils.

Make sure air conditioner does not fall during removal.

If unit does not operate after installation check, to be sure the circuit interrupter has not been tripped. Refer to the Troubleshooting guide for reset procedure.

Shim (2EA)

6"

 

 

6"

 

 

 

 

 

FIG. 23

8 Remove the metal rear grille and replace it with the plastic rear grille to improve unit energy efficiency. The plastic grille reduces the amount of hot air discharge that recirculates through the unit.

Plastic rear grille

Steel rear grille

FIG. 24

9 Install the new unit into the wall sleeve

10 Assemble trim as described in Step 6, Procedure A.