Frymaster HCFU-42CF03, HCFU-42HF03 Electrical Requirement, Installation of Indoor Unit

Models: HCFU-42HF03 HCFU-42CF03

1 29
Download 29 pages 32.4 Kb
Page 23
Image 23
ELECTRICAL REQUIREMENT

 Electric wire size and fuse capacity:Manual background Installation of Indoor Unit

ELECTRICAL REQUIREMENT

Manual background Electric wire size and fuse capacity:

Table 5

Series

 

HCFU-42CF03

 

HCFU-42HF03

 

 

 

Connection

 

MAX

3.5

cord

 

 

 

 

MIN

2.0

(mm2)

 

 

 

 

 

Fuse capacity(A)

 

30

 

 

 

 

Fig. 15

Insulation tube

Cord clamp

Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.

Manual background CAUTION

(1)Match the terminal block numbers and connection cord colors with those of the outdoor unit.

Erroneous wiring may cause burning of the electric parts.

(2)Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.

(3)Always fasten the outside covering of the connection cord with the cord clamp. (If the insulator is chafed, electric leakage may occur.)

(4)Always connect the ground wire.

21

Page 23
Image 23
Frymaster HCFU-42CF03 Electrical Requirement, Installation of Indoor Unit, Electric wire size and fuse capacity