1-20 SPARC Enterprise M4000/M5000 Servers Overview Guide • December 2010
1.3.6 Operator Panel
The operator panel (FIGURE1-15), which is not redundant, displays the system status,
system problem alerts, and location of system faults. It also stores the system
identificationand user setting information. For more information on the operator panel
functions, refer to theSPARC Enterprise M4000/M5000 Servers Service Manual.
TABLE1-7 CPU Typesand Maximum Power Consumption on the M4000 Server*
* M4000 system configuration: CPUM x 2, MEMB x 4, 8GB DIMM x 32, HDD x 2, PCIe x 4, PCI-X x 1, DAT x 1.
CPUType Frequency(GHz) Number
Power
Consumption(W)
Apparent
Power(VA) Heat Dissipation (KJ/h)
SPARC64 VI processor 2.15 4 1556 1621 5602
SPARC64 VII processor 2.4/2.53 4 1656 1725 5962
SPARC64 VII+ processor 2.66 4 1692 1763 6091
TABLE1-8 CPU Typesand Maximum Power Consumption on the M5000 Server*
* M5000 system configuration: CPUM x 4, MEMB x 8,8GB DIMM x 64, HDD x 4, PCIe x 8, PCI-X x 1, DAT x 1.
CPUType Frequency(GHz) Number
Power
Consumption(W)
Apparent
Power(VA) HeatDissipation (KJ/h)
SPARC64 VI processor 2.15 8 2998 3123 10793
SPARC64 VII processor 2.4/ 2.53 8 3198 3331 11513
SPARC64 VII+ processor 2.66 8 3270 3406 11772