Chapter 2 Preparing to Install the Server 2-3
TABLE2-1 ElectricalSpecifications for the M4000 Server
Parameter Value
Number of power cords 2 (1 power cord per power supply unit)
Redundancy 1+ 1 redundant.Second power supply is
redundantat 200 VAC
Input current Voltagerange 100–127 VAC
200–240 VAC
Current,maximum 24.0A at 100–127 VAC(12A per cord)
12.0A at 200–240 VAC(12A per cord)
Currentfrequency range 50–60Hz
Power draw (maximum) 1,692W (2 power cords)
Volt-ampere 1,763 VA
Heat 5,774 BTUs/hr (6,091 kJ/hr)
Power factor 0.98
TABLE2-2 ElectricalSpecifications for the M5000 Server
Parameter Value
Number of power cords 4 (1 power cord per power supply unit)
Redundancy 2 + 2 redundant. Second and fourth
power supplies are redundant at 200
VAC
Input current Voltagerange 100–127 VAC
200–240 VAC
Current,maximum 48A at 100–127 VAC(12A per cord)
24A at 200–240 VAC(12A per cord 2+2
redundancy)
Currentfrequency range 50–60 Hz
Power draw (maximum) 3,270W (4 power cords)
Volt-ampere 3,406 VA
Heat 11,160BTUs/hr (11,772 kJ/hr)
Power factor 0.98