Chapter 1 Physical Specification 1-31
1.2.3 Planning Your Access Route

This section describes necessary considerations before you move the server to its

installation destination.

1.2.3.1 Space Required for System Transport

The access route must satisfy the requirements listed in TABLE 1-4.

Each cabinet is packed with simple packaging or in a wood-framed case for shipping

of the server. If it is difficult to carry the packed cabinet to the installation

destination, remove the packing materials, front and rear doors, side panels, and/or

other parts as necessary.

If the cabinet weight exceeds the minimum withstand load for the transport

equipment used, you can move the cabinet with its PSU and FAN unit (about 4 kg

each) removed.

TABLE 1-4 Space Required for Transport (1 of 2)
Name
Device
status
during
transport 1
Minimum
door height
[mm (inch)]
Minimum
door width
[mm (inch)]
Minimum
passage
width [mm
(inch)]
Minimum
elevator car
depth [mm
(inch)]
Minimum
withstand
load of
transport
equipment
[kg] 3
Maximum
inclination
of access
route [° ]
SPARC
Enterprise
M8000 server
Simple
packaging11900 (74.8) 1000 (39.4) 1200 (47.2) 1500 (59.0) 820 10
Without
front and
rear doors
or side
panels
1900 (74.8) 800 (31.5) 1000 (39.4) 1350 (53.1) 690 10
Tri-Wa ll22100 (82.7) 1800 (70.9) 1800 (70.9) 1100 (43.3) 830 10
Wooden2
packing
2100 (82.7) 1900 (74.8) 1900 (74.8) 1100 (43.3) 980 10