3-14 SPARC Enterprise M8000/M9000 Servers Site Planning Guide • April 2008
3.4.1.2 Power Cable Connection SpecificationsTABLE 3-8 lists specifications for single-phase power supply connections.
The SPARC Enterprise M8000/M9000 servers are equipped with the required
number of single-phase power cables.
TABLE 3-8 Specifications (Single-Phase Power Supply Connections) (1 of 3)
Name Destination
Power cable
length 1Plug geometry
Number of
plugs Outlet in facility
SPARC
Enterprise
M8000
server
Japan 3.0m
(9.8 feet)
30A-250V 3P,
locking type
(NEMA L6-30R)
3 (single
power feed)
6 (dual power
feed)
30A-250V 3P, locking type
(NEMA L6-30R)
Embedded type: 3320-L6
<American Denki>
Exposed type: 3321-L6
<American Denki>
3.0m
(9.8 feet)
Parallel 2P+E
(conforming to
NEMA5-15P)
1 (FST) 15A-125V (conforming to
NEMA5-15R)
North America
General
overseas
3.0m
(9.8 feet)
NEMA L6-30P 3 (single
power feed)
6 (dual power
feed)
NEMA L6-30R (North
America only)
Europe 3.0m
(9.8 feet)
EN60309 (32A) 3 (single
power feed)
6 (dual power
feed)
EN60309 (32A)