Chapter 3 Environmental and Electrical Specifications 3-5
3.2.1 Single-Phase Power SuppliesTABLE 3-4 Specifications (Single-Phase Power Requirements) (1 of 2)
Name
Power supply
Power
consumption
[kW]
Apparent
power
[kVA]
Power
factor
Rush
current
[A0-p]
Leak
current
[mA]
Circuit
breaker
capacity
[A]
Volta ge
[V] Phase
Frequency
[Hz]
SPARC
Enterprise
M8000 server
200 to
240
VAC
±10%
Single 50/60
+2%, -4%
10.5 211.0 20.9 or
higher
100 or
less 64.1 or
less 630 7
100
VAC 3
±10%
0.1 3- - - - -
SPARC
Enterprise
M9000 server
(base cabinet)
200 to
240
VAC
±10%
21.3 422.4 40.9 or
higher
100 or
less 64.1 or
less 630 7
100
VAC 3
±10%
0.1 3- - - - -
SPARC
Enterprise
M9000 server
(base cabinet +
expansion
cabinet)
200 to
240
VAC
±10%
42.6 544.8 50.9 or
higher
100 or
less 64.1 or
less 630 7
100
VAC 3
±10%
0.1 3- - - - -
Power Cabinet
SPARC
Enterprise
M9000 server
(base cabinet) 1
200 to
240
VAC
±10%
21.3 422.4 40.9 or
higher
100 or
less 64.1 or
less 630 7