g

GE Digital Energy

 

8

- Specifications

 

NetPro 19” model

:

600

1000

1500

Ratings

:

600

1000

1500

Voltage Amperes (VA)

with computer type load

:

360

600

900

Watts (W)

with resistive load

:

5

5

7

Input thermal circuit breaker (A)

Input fuse (A)

:

8

8

10

Input converter

:

220 - 240 V

 

AC input voltage

 

AC input voltage range

:

100% load: 187 - 264 V

 

 

 

70% load: 120 - 264 V

 

 

 

input >264 Vac: UPS switches to battery operation

Minimum start-up AC voltage

:

input >312 Vac: UPS shuts down, manual restart required

187 V (at any load)

 

Input current waveform

:

sinusoidal

 

Input current (A) at nom. inp. volt.

:

conform or better than EN 61000-3-2 (IEC 555-2)

2.0

3.3

5.0

Input power factor

:

1

 

 

Input frequency range

:

45 - 66 Hz

 

Inrush current

:

none

 

 

Output converter

:

230 V (suitable for 220 - 240 V loads)

AC output voltage

AC output voltage tolerance

:

± 2%

 

 

Output frequency

:

50 or 60 Hz, front selectable

 

Output frequency range

:

nominal ± 0.15% unless synchronized to the mains

Output waveform

:

sine wave

 

Harmonic distortion

:

< 2% (typical 1.5%) with linear load

Power factor

:

0.6 (0.7 at 90% load)

 

Crest factor (peak to RMS current)

:

suitable for loads with c.f. up to 6:1

 

Capacity appliance outlets

:

max. 10 A per outlet

 

Bypass

:

195 - 264 V

 

AC input voltage range

 

Frequency tracking rate

:

2 Hz/sec.

 

 

Frequency tracking range

:

nominal ± 10%

 

Phase difference

:

< 7º

 

 

Typical transfer time, msec

:

4

 

 

Overload capability

:

Fully protected against overload and short circuits

Overload behaviour (battery operation)

:

110% during 5 minutes; 150% during 5 seconds

Overload behaviour during

:

depends on rating of thermal circuit breaker

bypass operation

 

typical:

125% of TCB value for 200 seconds

 

 

 

200% of TCB value for 10 seconds

 

 

 

300% of TCB value for 4 seconds

Batteries (ratings given for 25ºC)

:

24

36

48

Nominal voltage (Vdc)

Number of 7 Ah batteries

:

2

3

4

Type

:

sealed lead acid, maintenance free

Service life

:

up to 6 years (depending on use)

 

Recharge current

:

1.5 A

 

 

Battery recharge time

:

1.5 hours for 90% capacity, std battery

(batt. discharged at 100% load)

Runtime in minutes

:

12

12

10

at typical load (75%)

VA/Watts

:

64

104

124

100/60

200/120

:

34

54

71

400/240

:

15

27

36

600/360

:

9

15

24

1000/600

:

-

9

12

1500/900

:

-

-

6

General

:

14

14

14

Weight without battery drawer (kg)

Weight with battery drawer (kg)

:

19

22

24

Dimensions (hxwxd, mm)

:

133.5 (3HU) x 450 (19”) x 440

 

Depth required in 19” rack (mm)

:

420 (without connectors)

 

Enclosure / protection

:

steel - plastic / IP20

 

Environment

:

EN 50091-1-1, EN 60950, IEC 950

 

Safety

 

Electromagnetic compatibility

:

EN 50091-2

 

Ambient temperature

:

-10 to +40ºC

 

Audible noise at 1 meter

:

< 45 dB(A), load and temperature dependent

Max. relative humidity

:

95% (non-condensing)

 

 

 

 

 

OPM_NPE_19X_600_1K5_2GB_V030

 

13

GE DE NetPro 19” 600-1500: User manual 3.0 (GB)

Page 14
Image 14
GE 600 - 1500 VA manual Specifications, NetPro 19 model 600 1000 1500 Ratings