g
GE Digital Energy
4 - Communication
4.1RS232 Port (fig. 8)
The RS 232 Port is a
We strongly recommend to use only original GE Digital Energy software products in combination with the interface port.
Pin # | Function | fig. 8 | |
1 | RS232 input (UPS shutdown) | ||
| |||
2 | RS232 output |
| |
3 | General alarm1) |
| |
4 | Plug and Play |
| |
5 | Common |
| |
6 | Bypass active |
| |
7 | Battery low |
| |
8 | UPS connected |
| |
9 | Mains failure |
|
1) Active if the output voltage of the UPS is no longer guaranteed due to other circumstances than already indicated by pin
- Output converter overload
- Overtemperature
- Bypass out of limits
- Inverter shutdown (due to inverter failure or batt. failure)
5 = COMMON
8 = UPS CONNECTED
MAINS FAILURE |
| |||
| DC |
| 5 | |
PnP |
| 9 | ||
RS232 | ||||
| 4 | |||
|
|
| ||
GENERAL ALARM | 8 | |||
3 | ||||
|
|
| ||
BATTERY LOW |
| 7 | ||
| 2 | |||
|
|
| ||
|
|
| 6 | |
BYPASS ACTIVE | 1 | |||
DATA FROM | DC | RS232 | ||
UPS |
| RS232 | PORT | |
DATA TO UPS | DC |
| ||
REMOTE UPS | RS232 |
| ||
|
| |||
SHUT DOWN |
|
| ||
MAX: +48V 100mA |
|
|
4.2Relay Interface Card (option)
The card is equipped with potential free
•mains failure
•general alarm
•battery low
•bypass active
For more information please refer to the user manual that comes with the interface card.
4.3SNMP Interface Card (option)
This card allows the data interface to be connected directly to an Ethernet network.
For more information please refer to the user manual that comes with the interface card.
OPM_NPE_19X_600_1K5_2GB_V030 | 9 | GE DE NetPro 19” |