Configuration Guide

ERR 2101: INVALID OFFSET, REC <xx>

Why:

The LRU Offset entry for the indicated A016_XRF record number is not within the valid entry range described earlier in this document.

Remedy:

Modify and re-download the configuration with a correct entry in the specified configuration record.

ERR 2200: INVALID LOCAL/REMOTE POINT, REC <xx>

Why:

The Local/Remote entry for the indicated A016_LRU record number is not within the valid entry range described earlier in this document.

Remedy:

Modify and re-download the configuration with a correct entry in the specified configuration record.

ERR 2201: INVALID LOCAL STATE, REC <xx>

Why:

The Local State entry for the indicated A016_LRU record number is not within the valid entry range described earlier in this document.

Remedy:

Modify and re-download the configuration with a correct entry in the specified configuration record.

ERR 2202: INVALID FREEZE POINT, REC <xx>

Why:

The Freeze Output entry for the indicated A016_LRU record number is not within the valid entry range described earlier in this document.

Remedy:

Modify and re-download the configuration with a correct entry in the specified configuration record.