CHAPTER 12
EXITING THE PROGRAMMING MODE
NOTE: STEPS TO EXIT THE PROGRAMMING MODE VARIES AS THE PROGRAMMING STAGE VARIES.
Exiting the Programming Mode is ALWAYS necessary to store any new changes and to calculate a new checksum.
Failure to exit results in a checksum error. The display blanks and the max LED intermittently flashes.
IF YOU ARE LOCATED AT: F
UNCTION LEVEL - begin at Step 1
GROUP LEVEL - begin at Step 2
MAX
AC VOLTS
A B C N
AC AMPS
MAX/MIN
LIMITS VOLTS
PRINT
PROG
PHASE
NEXT
00.
AMPS
B C A
I I I
A B C
N N N
I I I
A B C
LM2
LM1MIN
I25
MAX
AC VOLTS
A B C N
AC AMPS
MAX/MIN
LIMITS VOLTS
PRINT
PROG
PHASE
NEXT
IE.
AMPS
B C A
I I I
A B C
N N N
I I I
A B C
LM2
LM1MIN
MAX
AC VOLTS
A B C N
AC AMPS
MAX/MIN
LIMITS VOLTS
PRINT
PROG
PHASE
NEXT
E.
AMPS
B C A
I I I
A B C
N N N
I I I
A B C
LM2
LM1MIN
EXITING FROM FUNCTION LEVEL EXITING FROM GROUP LEVEL
Step 1:
a. Press MAX/MIN/ LIMITS until the
Group number in upper display is
followed by E.
ÖThe EPM3000P returns to Function
Level.
Step 1a:
a. Press VOLTS to exit from
Function Level to Group Level.
Step 2:
a. Press MAX/MIN/ LIMITS until E.
appears in upper display.
b. Press VOLTS to exit entirely from
Programming Mode.
YOU HAVE EXITED THE PROGRAMMING MODE.
AFTER A MOMENT, THE METER RETURNS TO THE OPERATING MODE.
41