Th ermostats automat ical ly reset after th e mot or h as cooled somewhat. In order

to preven t pro pert y damag e or injury to personnel, the control circuit should be

designed to prevent re-en ergizing of the motor when the thermostat resets.

Table 5
Maximum Current Ratings for Thermostats
on Dripproof and Totally Enclosed Motors
(Normally open or normally closed con tacts)
Load 125 VAC 250 VAC 600 VAC 30 VDC
Do not use above 600 V A C or 30 V DC
Resistive 5Amps 2.5Amps 1Amp 5Amps
Inductive* 3 Amps 1.5 Amps 0.5 Amps 1.5 Amps
*Sui tabl e for pil ot duty only (r elay coil s).
H. Speed Li mit Devic e
The mech anical speed limit device is non-adjustable. Tripping speed is specified by a note on the print cer-
tification for each specific order.
The speed limit electrical con tacts are normally closed and are usually conn ected in relay or h olding circuits.
Current ratin gs are the same as those listed in Table 5.
A speed limit device is furnished on machin es only wh en ordered.

Th e con tacts of th e speed l imi t devi ce aut omati call y reclo se after t he speed has

fallen below the trip value. In order to prevent property damage or injury to

personnel, the control circuit should be designed to prevent re-energizing the

motor until the cause of t he overspeed has been corrected.

Table 6
Lead M arkers
Function Winding
Armat ur e A1, A 2
Fiel d ( S hunt) F1, F2, F3, F 4, etc.
Stator, AC Machines Only T1, T2, T3, T4, etc.
(Ty pe A N Tachometer Generator )
Accessories & Sp ecial Device Markings
Tachometer Gener ator, Direct Current , to T er minal B oar d A1, A 2
Brake Coil Leads B1, B 2, B3, B 4, etc.
Heater, Brak e S pac e Heater BH1, B H2, BH3, B H4, etc.
Brake Interlock Switch BS1, BS2, BS3, BS4, etc.
Heater, Space Heater i n the Machine H1, H2, H3, H4, etc.
Thermostat P1, P2, P3, P4, etc.
Resistance T emper ature Detec tor (RT D) R1, R2, R3, R4, etc.
I. Space Heat er
When furnished, see Prin t Certification for Electrical Rating.
Space heaters are fur nished in machin es wh en ordered. They should be energized with the corr ect AC volt-
age as shown on the nameplate.