Dirt can be removed from stationary parts of the machine by either compressed air or a vacuum nozzle or a
combination of both. Air should be directed between the stator coils, into the pocket corners of bearing
brackets, around the cables and onto the brush rigging. Special care should be taken to keep th e commutator
clean. The commutator should be wiped with a clean lin t-free cloth after blowing out.
Safety glasses and/or other protective equipment should be used to prevent
injury to eyes and respi rat ory o rgans.
High voltage electric shock can cause serious or fatal injury. Electrical circuits
must be de-energized prior to cleaning or other maintenance activities. Ground
electrical circuits prior to cleaning or maintenance to discharge capacitors.
Fai lu re t o observe these precautions may result i n injury to personnel.
Liquid solvents should not be directly applied to the commutator, armature,
field coils or any electrical part of a DC machine. Liquid solvents carry con-
ducting contaminants (metal dust, carbon, etc.) deep into hidden areas to pro-
duce shorts and grounds, thus causing machine failure. Mechanical compo-
nen t s may be cl eaned by a wiping rag barely mo istened ( not wet) wi t h a solven t .
Solvents may be flammable and moderately toxic. The usual precautions for
handling chemicals of this type must be observed. These in clude:
1. Avoid excessive co ntact wi t h skin.
2. Use in well venti lated areas.
3. Take n ecessary precautions to prevent f ire or explosion hazards.
1. Oily Dirt
The presence of oil makes thorough, effective cleaning of machines in service virtually impossible and
service shop conditioning is recommended. Oil on a surface forms a “fly paper effect”, wh ich attracts
and holds firmly any entrained dust. Neither suction nor compressed air is effective. Consequently,
only accessible areas may be cleaned. First, remove as much of the dirt as possible by scraping or
brushing the dirty surfaces. Then, wipe away as much dirt as possible with dry r ags. For surfaces not
readily accessible, a rag on a hook wire can be used to clean dirt out of holes and crevices. Rags
should be changed frequently for clean ones so that con tamination picked up fr om one area is not car-
ried to other less dirty areas.
While FREON TF



is considered to be nonflammable and has a relatively low
order of toxicity, it should be used only in well ventilated areas that are free
from open flames. Avoid prolonged exposure to vapors. Failure to observe
these precau t ions may result i n injury to personnel.
FREON TF is the only recommended solvent for cleaning because it is nonflammable, has good sol-
vency for grease and oil, is con sidered safe with most varnishes and insulations an d has a low order of
toxicity. Stoddard solvent has good solvency, but is flammable and moderately toxic. Before using
any solvent, consult the Material Safety Data Sheet. Steam cleaning is not recommended because, as
with liquid solvents, conducting contamin ants may be carr ied deep into inaccessible areas resulting in
shorts and grounds.