Electrical Connections

Installation Instructions

B

Electrical Connections

ATTENTION INSTALLER

All electric wall ovens must be hard wired (direct wired) into an approved junction box. A plug and receptacle is NOT permitted on these products.

DO NOT shorten the flexible conduit. The conduit strain relief clamp must be securely attached to the junction box and the flexible conduit must be securely attached to the clamp. If the flexible conduit will not fit within the clamp, do not install the oven until a clamp of the proper size is obtained.

Turn off the circuit breaker or remove fuses

B1 to the oven branch circuit.

With the oven supported on a table or

B2 platform in front of the cabinet opening, connect the flexible conduit to the electrical junction box as shown below. Position the conduit in such a manner that it will lie on top of the oven in a natural loop when the oven is installed. You will need to purchase an appropriate strain relief clamp to complete the connection of the conduit

to the junction box.

Junction Box

Location

NOTE TO ELECTRICIAN: The 3 power leads supplied with this appliance are CSA recognized for connection to heavier gauge household wiring. The insulation of these 3 leads is rated at temperatures much higher than the temperature rating of household wiring. The current carrying capacity of the conductor is governed by the wire gauge and the temperature rating of the insulation around the wire.

ATTENTION INSTALLER WARNING: Improper

connection of aluminum house wiring to copper leads can

Conduit

Place oven on a support to assist in connecting conduit

GROUND

WIRE

BARE

GROUND RED

 WARNING: ImproperManual backgroundManual backgroundManual background WHITE

BLACK

Strain Relief Clamp (not included) must be used at Junction Box

result in an electrical hazard or fire. Use only connectors designed for joining copper to aluminum and follow the manufacturer’s recommended procedure closely.

This oven is supplied with a 123 cm (48)

B3 long flexible conduit consisting of:

3 insulated conductors (copper)

1 bare ground conductor (copper)

Attach conductors to residence wiring as

B4 shown by wiring diagram.

9

CONDUIT

 

 

FROM

 

WHITE

OVEN

 

(NEUTRAL)

 

RED

 

 

BLACK

 

 

BARE

 

 

COPPER

 

 

 

WHITE

 

BLACK

RED

 

 

 

GROUND

 

CSA APPROVED Manual background

JUNCTION BOX AND COVER

CSA APPROVED

CONNECTOR

TO BREAKER PANEL #12-#10 AWG-COPPER NMD90 WIRE. FUSE 20 AMP CIRCUIT BREAKERS