Receptacles/Sub-bases
Tandem | Perpendicular | Large tandem | 265V 15 Amp | 265V 20 Amp |
| 265V 30 Amp | ||||
230/208V 15 Amp | 230/208V 20 Amp | 230/208V 30 Amp |
| |||||||
| receptacle used | receptacle used | ||||||||
|
|
|
|
|
| On 265V | On 265V | |||
|
|
|
|
|
|
| GE073 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| RAK204U |
| RAK204D15P | RAK204D20P | RAK204D30P | RAK204E15 |
| RAK204E20 |
| RAK204E30 |
Voltage | N/A |
| 0/208 | 0/208 | 0/208 | 5 |
| 5 |
| 5 |
Amps | N/A |
| 15 | 0 | 0 | 15 |
| 0 |
| 0 |
Receptacle | N/A |
|
|
|
230/208 Volt
265 Volt units are to be direct connected. Cordset through enclosed chaseway into interior
Power connection kits are required on all Zoneline® chassis (see chart below).
The correct kit for the installation is determined by the voltage and amperage of the electrical circuit and the means of connecting the unit to the building wiring. If the unit is to be plugged into a receptacle, a line cord kit would be used; if the unit is to be permanently connected, a permanent connection kit would be used. 265 volt cord set units must be installed in compliance with National Electrical Code®.
Power connection kits
Required on all models. See specification sheet for heater KW and branch circuit ampacity.
RAK3153/3203 | RAK4157/4207/4307 | RAK5157/5207/5307 |
230/208 volt line cord | 230/208 volt universal | 265 volt universal power |
connection kit | power supply kit | supply kit |
230/208 volt | Line cord connected units |
| ||
LCDI Power Connection Kit | RAK3153 | RAK3203 |
| RAK3303 |
Heater KW | 2.55/2.09 | 3.45/2.82 |
| 5.00/4.09 |
Watts | 2,550/2,090 | 3,450/2,820 |
| 5,000/4,090 |
BTUH | 8,600/7,100 | 11,700/9,600 |
| 17,000/13,900 |
Amps | 11.6/10.6 | 15.6/14.2 |
| 22.4/20.4 |
Min. circuit amps | 15 | 20 |
| 30 |
Recommended | 15 amp | 20 amp |
| 30 amp |
protective | time delay | time delay |
| time delay |
device | fuse or breaker | fuse or breaker |
| fuse or breaker |
265 volt Permanent connected units* (Cord set)
RAK5172 | RAK5202 | RAK5302 |
2.55 | 3.45 | 5.0 |
2,550 | 3,450 | 5,000 |
8,600 | 11,700 | 17,000 |
10.3 | 13.8 | 19.6 |
15 | 20 | 30 |
15 amp | 20 amp | 30 amp |
time delay fuse | time delay fuse | time delay fuse |
*To be used with
230/208 volt |
| Direct connection kit** |
| ||
| RAK4157 |
| RAK4207 |
| RAK4307 |
|
|
| |||
Heater KW | 2.55/2.09 |
| 3.45/2.82 |
| 5.00/4.09 |
Watts | 2,550/2,090 |
| 3,450/2,820 |
| 5,000/4,090 |
BTUH | 8,600/7,100 |
| 11,700/9,600 |
| 17,000/13,900 |
Amps | 11.6/10.6 |
| 15.6/14.2 |
| 22.4/20.4 |
Min. circuit amps | 15 |
| 20 |
| 30 |
Recommended | 15 amp |
| 20 amp |
| 30 amp |
protective | time delay |
| time delay |
| time delay |
device | fuse or breaker |
| fuse or breaker |
| fuse or breaker |
**To be used with
265 volt Direct connection kit**
RAK5157 | RAK5207 | RAK5307 |
2.55 | 3.45 | 5.0 |
2,550 | 3,450 | 5,000 |
8,600 | 11,700 | 17,000 |
10.3 | 13.8 | 19.6 |
15 | 20 | 30 |
15 amp | 20 amp | 30 amp |
time delay fuse | time delay fuse | time delay fuse |
**To be used with
10