Digital EnergyGT Series

6.3.2Battery replacement procedure) 1.5kVA 1 Remove front panel

2 Unscrew two bolts of the

3 battery terminal cover and remove it

4 Unplug battery connectors

5 Unscrew five bolts of the

6 battery compartment cover and remove it

7 Unscrew two bolts of battery fixer and remove it

8 Pull out the battery set and renew it

9 Assemble UPS

by reverse procedure.

Fig. 6.2

6.3.3Battery replacement procedure) 3kVA

NOTE: The battery banks should be installed by service personnel.

1Remove front panel

2Unscrew two bolts of the battery compartment

3Remove battery cover

4Unscrew two bolts

5/6 Remove stop holder and battery terminal 7 Grasp the tag to pull out the battery sets.

Be careful, heavy weight! Notice not to let the battery set to drop in accident

7When you see the first warning label, please disconnect all leads

Continue horizontally pulling the battery set 1 until you see the next warning label (See fig. 6-4)

7a Now you can easily release battery set 1! (Gently lift it up!) Put battery set 1 beside.

7b Continue pulling out battery set 2.

8Unplug all connectors of batteries

9Renew the batteries and re-install them with reverse procedure.

Fig. 6.3

Fig. 6.4

6.4Recycling the UPS at the end of service life

GE Digital Energy, in compliance with environment protection recommends that the UPS equipment, at the end of its service life, must be recycled conforming to the local applicable regulations.