Digital Energy™ GT Series
4.2RS232
The
1 - Monitoring charger status
2 - Monitoring battery status and condition
3 - Monitoring inverter status
4 - Monitoring UPS status
5 - Monitoring the AC utility power status
6 - Turn on/off UPS on schedule for power saving 7 - Adjust transfer voltage
Pin Assignment:
Pin 2 : PC receives line
Pin 3 : PC transmits line
Pin 5 : Signal ground.
Pin 4,6,7: Reserved for plug and play function.
The UPS data is provided at 2400 bps baud rate and made up of
Hardware:
Baud rate | 2400 bps |
Data length | 8 bits |
Stop bit | 1 bit |
Parity | none |
Cabling:
Standard
4.3Dry Contact
Its major functions are some or all of the following:
1 - to broadcast a warning when the AC utility power fails. 2 - to save open files before the battery is exhausted.
3 - to turn off the UPS via computer(s).
Pin Assignment:
Pin 1 : Normally open. When the battery voltage level is low, pin 1 and pin 5 are connected together via a photo coupler.
Pin 3 : UPS will shut down when a high level (5~12V) is applied for at least 3.8 seconds.
Pin 5 : Signal ground.
Pin 6,7 : Reserved.
Pin 8 : Normally open. When the AC utility fails, pin 8 and pin 5 are connected together via a photo coupler.
Cabling:
A special cable must be used with a pin assignment as follows:
PC (female) | UPS (male) | |
Pin 1 | Pin 1 (Battery Low) | |
Pin 3 | Pin 5 (GND) | |
Pin 4 | Pin 3 | (Shutdown) |
Pin 7 | Pin 6 |
|
Pin 7 | Pin 7 | (AC Fail) |
Pin 8 | Pin 8 |
OPM_GTU_19X_1K0_3K0_XUS_V014 | 15 |