Fig. 3.9 Bypass operation

g

Digital EnergyGT Series

3.4.4Bypass operation

If the UPS is unable to deliver the

demanded output power due to overload or over-temperature, the load is switched directly to the utility supply.

The LED ‘Bypass’ will light, and the buzzer will sound continuously.

The UPS will switch back to ‘ON LINE’ mode (normal operation) when the load and/or temperature conditions returned to normal.

If a power failure occurs during bypass operation, the UPS will switch to battery operation and eventually, when the batteries

are depleted, UPS output power is lost. If the UPS functions under overload or over- temperature conditions it may not be able to protect the load.

3.4.5Replace battery

The batteries are aged and must be replaced as soon as possible to ensure full protection for your equipment.

The ‘Replace Battery’ LED lights and the buzzer sends out three beeps every hour, until the batteries have been replaced.

Fig. 3.10 Replace battery

3.4.6Short circuit

In case of a short circuit in the load during ‘ON-LINE’ mode or ‘ON BATTERY’ mode the UPS will shut down and output power is lost.

The Fault LED will light and the buzzer will sound continuously.

The situation will be cleared if the short

circuit is removed.

If the short circuit situation happens during ‘BYPASS’ mode, the input breaker will trip and the UPS output power is lost.

Fig. 3.11 Overload

OPM_GTU_19X_1K0_3K0_XUS_V014

13

GT-UL Series: User manual 1.2 (US)

Page 14
Image 14