g

GE Capacitor & Power Quality Products

INSTALLATION INSTRUCTIONS - continued

Table 8

Input and Output Terminal Specifications

Filter

Input Terminals

Output Terminals

Rating(Amps)

 

 

 

 

 

Wire Range

Terminal Torque

Wire Range

Terminal Torque

 

(AWG)

(in-lbs)

(AWG)

(in-lbs)

6

22 -14

4.5

22 – 14

4.5

8

 

 

 

 

11

22 - 14

4.5

22 – 14

4.5

14

22 - 14

4.5

22 – 5

16

21

22 - 5

16

22 – 5

16

27

22 - 5

16

22 – 5

16

34

22 - 5

16

18 – 4

20

44

22 - 5

16

18 – 4

20

52

18 – 4

20

18 – 4

20

66

18 – 4

20

6-4

45

2-0

50

 

 

 

 

 

 

 

 

83

6-4

45

6-4

45

2-0

50

2-0

50

 

 

 

 

 

 

103

6-4

45

6-4

45

2-0

50

2-0

50

 

128

6-4

45

6-4

45

2-0

50

2-0

50

 

165

6-4

45

2-0000

150

2-0

50

 

 

 

208

2 – 0000

150

2 – 0000

150

240

2 – 0000

150

2 – 0000

150

 

 

 

00

180

320

2-0000

150

000-0000

250

250-350 MCM

325

 

 

 

 

 

 

500 MCM

375

 

00

180

00

180

403

000-0000

250

000-0000

250

250-350 MCM

325

250-350 MCM

325

 

 

500 MCM

375

500 MCM

375

 

00

180

00

180

482

000-0000

250

000-0000

250

250-350 MCM

325

250-350 MCM

325

 

 

500 MCM

375

500 MCM

375

636

NA

NA

NA

NA

786

NA

NA

NA

NA

GEH-7252

30

May 2003

Page 33
Image 33