GE SERIES B 480 user manual GE Capacitor & Power Quality Products

Models: SERIES B 480

1 53
Download 53 pages 58.06 Kb
Page 50
Image 50

g

GE Capacitor & Power Quality Products

3.Check that moisture has not condensed on the filter components. If moisture is present, do not proceed with startup until the moisture has been removed.

4.Disconnect the filter output from the drive.

5.Connect the filter to the utility.

WARNING

Use extreme caution to avoid contact with line voltage when checking for power. INJURY OR DEATH MAY RESULT IF SAFETY PRECAUTIONS ARE NOT OBSERVED.

6.Confirm that line voltage is present at the input terminals (A1, B1, C1) of the filter.

7.Confirm that line voltage is present at the output terminals (A2, B2, C2) of the filter.

8.Disconnect the filter from the utility.

9.Connect the filter output to the drive.

10.Refer to the drive user manual for the drive startup procedure. Observe all safety instructions in the drive user manual.

WARNING

INJURY, DEATH AND/OR PROPERTY DAMAGE MAY RESULT IF THE DRIVE SAFETY PRECAUTIONS ARE NOT OBSERVED.

CAUTION

DAMAGE TO EQUIPMENT MAY OCCUR IF THE DRIVE STARTUP PROCEDURES ARE NOT OBSERVED.

GEH-7252

47

May 2003

Page 50
Image 50
GE SERIES B 480 user manual GE Capacitor & Power Quality Products, Disconnect the filter output from the drive