RM4 Control Interface (Optional ) (cont’d)
DANGER
HAZARDOUS VOLTAGE
(Can Cause Severe Injury or Death)
Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.
Automatic Generator Exerciser
The automatic generator exerciser comes preset with a
DANGER
Turn OFF all power before selecting.
JP (CDT SELECT)
selectable through (JP) jumper selection on the con- troller board. The selections are 7, 14, 21 or 28 day.
Selecting Exerciser Without Transfer
To start the automatic exerciser without transfer, depress the Exerciser Start/Stop button. The generator will start and run for 10 minutes.* Once this first exercise is com- plete, the generator LED will flash at a
7 Day
4 5 6
BA
14 Day
4 5 6
B A
See Figure 3, Page 4
21 Day
4 5 6
BA
28 Day
4 5 6
B A
JP (VOLTAGE/FREQUENCY SELECT)
Selecting Exerciser With Transfer
To enable the automatic exerciser with transfer, depress the Exerciser Start/Stop button and the transfer button. The generator will start and the load will be transferred to the generator. After 10 minutes*, the load will be transferred back to the utility. Once this first exercise is complete, the generator LED and the Generator position LED will flash at a
*Pressing and releasing the generator Start/Stop button will cancel the current test. The exerciser will go off at approximately the same time it was started (7, 14, 21 or 28 days) later.
NOTE: Transfer will cause short interruption of power.
See Figure 3, Page 4
Do not adjust the jumper positions.
This service to be performed by qualified personnel only.