Section 2 — Installation

Liquid-cooled 15, 20 and 25 kW Generators

The recommended battery is Group 26, 12VDC, 550 CCA/75 AH minimum. All batteries must be at 100 percent state-of-charge before they are installed on the generator.

When using maintenance-free batteries, it is not nec- essary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals specified in Section 4, “Maintenance.” A negative ground system is used. Battery connections are shown on the wiring diagrams. Make sure all batter- ies are correctly connected and terminals are tight. Observe battery polarity when connecting batteries to the generator set.

NOTE:

Damage will result if the battery connections are made in reverse.

2.12 PREPARATION BEFORE START-UP

The instructions in this section assume that the standby generator has been properly installed, serv- iced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules” on pages 2 and 3, as well as all other safety information in this manual, before attempting to operate this (and related) equip- ment.

‹2.12.1 PRIOR TO INITIAL START-UP

Prior to initially starting the generator, it must

!be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quantities of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.

Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to Section 4, “Maintenance.”

‹2.12.2 TRANSFER SWITCH

If this generator is used to supply power to any elec- trical system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents elec- trical backfeed between two different electrical sys- tems, (for additional information, see the applicable transfer switch manual for this unit). The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compliance with applicable codes, standards and regulations.

‹2.12.3 FUEL SYSTEM

Make sure the fuel supply system to the generator (a) delivers the correct fuel at the correct pressure and volume and, (b) is properly purged and leak tested according to code. No fuel leakage is permitted.

‹2.12.4 GENERATOR SET LUBRICATION

Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” and “Engine Oil Recommendations”.

NOTE:

This engine is shipped from the manufacturer with 15W-40 oil. This oil should be changed after 30 hours of operation.

‹2.12.5 ENGINE COOLANT

Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” and “Coolant”.

‹2.12.6 BELT TENSION

Check the engine fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approximately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8- inches (10 to 16 mm).

‹2.12.7 ELECTRICAL SYSTEM

Make sure the generator is properly connected to an approved earth ground and/or ground rod.

Make sure the generator battery is fully charged, properly installed and interconnected, and ready for use.

Check to ensure that there are no loose electrical con- nections. Restrain any loose wires to keep them clear of any moving generator set components.

14

Page 16
Image 16
Generac 005030-0, 005028-0, 005031-0 owner manual Preparation Before START-UP

005028-0, 005030-0, 005028-0, 005031-0 specifications

Generac's line of generator models, including the 005028-0, 005030-0, 005031-0, and their closely related variant 005028-0, represent a fusion of durability, technology, and user-centric design focused on providing reliable power solutions for residential and commercial applications.

The Generac 005028-0 model stands out with its robust construction and efficient performance. It features a powerful engine that ensures a steady supply of electricity, capable of handling essential appliances during power outages. The model incorporates Generac's patented TruePower technology, which offers clean and stable power, ensuring sensitive electronics are safe from fluctuations. This feature is particularly appealing for homeowners who rely on medical equipment or sophisticated devices that require consistent power quality.

On the other hand, the 005030-0 model takes performance up a notch by equipped with a larger fuel tank, allowing for extended runtime during outages. It also has a quieter operation compared to its counterparts, making it suitable for residential areas where noise levels are a concern. The model includes an intuitive user interface that simplifies operation, letting users monitor their generator’s status effortlessly.

Similarly, the 005031-0 model boasts enhanced technology via a fully automatic transfer switch. This feature enables seamless switching between utility power and generator power without user intervention, ensuring that homes and businesses remain powered even during unexpected power failures. Equipped with advanced safety features, this model ensures that the generator operates only when necessary, significantly extending its lifespan and maintaining efficiency.

Additionally, all these Generac models share a durable casing designed to withstand harsh weather conditions. They are engineered for easy maintenance, with oil and fuel access points conveniently located for user convenience. Furthermore, the models come with various options for fuel types, including propane and natural gas, providing users flexibility based on their needs.

In summary, Generac's 005028-0, 005030-0, and 005031-0 models are characterized by their reliable performance, advanced technology, and user-friendly features. These generators are perfect solutions for anyone seeking a dependable source of backup power, ensuring that essential equipment runs smoothly without interruptions, no matter the situation.