Section 4 — Maintenance

Liquid-cooled 15, 20 and 25 kW Generators

4.10 SCHEDULED MAINTENANCE

The following is a recommended maintenance schedule for small standby and residential generator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application. They will need to be decreased (performed more frequently) if the unit is used in a severe application. Use calendar time from the previous maintenance interval to determine the next required maintenance interval.

Service Maintenance Interval Information:

The various service maintenance intervals are designated by interval numbers as follows:

1An early inspection of the generator set to insure it is ready to operate when required and to identify any poten- tial problem areas.

Performed monthly this requires approximately .5 man-hours per unit to complete.

This inspection may be performed by the end user providing the following safety steps are taken to prevent the engine from starting automatically without warning:

To prevent injury, perform the following steps in the order indicated before starting any maintenance:

Disable the generator set from starting and/or connecting to the load by setting the control panel AUTO/OFF/MANUAL switch to the OFF position.

Remove the 5 amp and 15 amp control panel fuses.

Turn off the battery charger (turn OFF utility supply to ATS).

Remove the negative battery cable.

The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condi- tion from burning out sensitive control panel components and circuits.

Following all maintenance, reverse these steps to assure the unit is returned to standby setup for normal operation when required.

2A break-in service inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed ONLY ONCE following the first three months of operation after purchase of the unit and requires approximately 2.5 man-hours per unit to complete.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

3An operational inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed semi-annually this requires approximately 1.5 man-hours per unit to complete.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

4A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed annually this requires approximately 4.0 man-hours per unit to complete.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

24

Page 26
Image 26
Generac 005030-0, 005028-0, 005031-0 owner manual Scheduled Maintenance, Service Maintenance Interval Information

005028-0, 005030-0, 005028-0, 005031-0 specifications

Generac's line of generator models, including the 005028-0, 005030-0, 005031-0, and their closely related variant 005028-0, represent a fusion of durability, technology, and user-centric design focused on providing reliable power solutions for residential and commercial applications.

The Generac 005028-0 model stands out with its robust construction and efficient performance. It features a powerful engine that ensures a steady supply of electricity, capable of handling essential appliances during power outages. The model incorporates Generac's patented TruePower technology, which offers clean and stable power, ensuring sensitive electronics are safe from fluctuations. This feature is particularly appealing for homeowners who rely on medical equipment or sophisticated devices that require consistent power quality.

On the other hand, the 005030-0 model takes performance up a notch by equipped with a larger fuel tank, allowing for extended runtime during outages. It also has a quieter operation compared to its counterparts, making it suitable for residential areas where noise levels are a concern. The model includes an intuitive user interface that simplifies operation, letting users monitor their generator’s status effortlessly.

Similarly, the 005031-0 model boasts enhanced technology via a fully automatic transfer switch. This feature enables seamless switching between utility power and generator power without user intervention, ensuring that homes and businesses remain powered even during unexpected power failures. Equipped with advanced safety features, this model ensures that the generator operates only when necessary, significantly extending its lifespan and maintaining efficiency.

Additionally, all these Generac models share a durable casing designed to withstand harsh weather conditions. They are engineered for easy maintenance, with oil and fuel access points conveniently located for user convenience. Furthermore, the models come with various options for fuel types, including propane and natural gas, providing users flexibility based on their needs.

In summary, Generac's 005028-0, 005030-0, and 005031-0 models are characterized by their reliable performance, advanced technology, and user-friendly features. These generators are perfect solutions for anyone seeking a dependable source of backup power, ensuring that essential equipment runs smoothly without interruptions, no matter the situation.