Generac 005030-0, 005028-0, 005031-0 Manual Retransfer And Shutdown, Automatic Operation

Models: 005028-0 005030-0, 005028-0, 005031-0

1 60
Download 60 pages 32.51 Kb
Page 19
Image 19
3.4MANUAL RETRANSFER AND

Section 3 - Operation

Liquid-cooled 15, 20 and 25 kW Generators

6.Reduce load to 3/4, 1/2, 1/4 and no load. Decrease the stability pot if there is instability at any load point.

7.Adjust differential pot to make the recovery to load changes even faster and minimize load change undershoot and overshoot. If it is set too high, it may introduce oscillations at some load. It can be set to zero (full CCW) if a small amount causes oscillations at some load.

8.Leave DIP switch 8 in TEST mode.

1.Place the AUTO/OFF/MANUAL switch in the AUTO position (Figure 3.3).

2.Press and hold the “Set Exercise Time” switch for five seconds, then release.

At this time all five red LEDs will flash for approxi- mately 10 seconds, then the engine will start and run for it’s 12 minute exercise period, then shut down. The generator will now start and run each week at the same time.

3.4MANUAL RETRANSFER AND

SHUTDOWN

When utility power source voltage has been restored, electrical loads may be transferred back to that source and the generator can be shut down as fol- lows:

Verify that utility power supply voltage to the trans- fer switch has been positively turned Off, using whatever means provided (such as utility main line circuit breaker).

Set the generator’s main circuit breaker to its Off or Open position.

Let the generator engine run at no-load for a few minutes, to stabilize internal unit temperatures.

On the generator console, set the Auto/Off/ Manual switch to Off. Wait for engine to come to a complete stop.

For transfer to utility position, refer to the Owner’s Manual of the particular transfer switch.

Turn on the utility power supply to the transfer switch, using whatever means provided (such as a utility main line circuit breaker). The utility power source now powers the loads.

3.5AUTOMATIC OPERATION

To set the system for fully automatic operation, pro- ceed as follows:

Check that load circuits are connected to the utility power supply.

Set the AUTO/OFF/MANUAL switch to its AUTO position.

Set the generator main circuit breaker to its ON or CLOSED position.

Figure 3.3 - “Set Exercise Time” Switch

RED LED'S = INDIVIDUAL FAULT

(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)

 

AUTO

OFF

 

 

OFF

ON

 

SET

MANUAL

EXERCISE

 

TIME

 

TO SET EXERCISER TIME

1)PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.

2)HOLD "SET EXERCISE TIME" SWITCH IN "ON" POSITION FOR THREE SECONDS AND RELEASE. (SEE OWNER'S MANUAL FOR COMPLETE DETAILS)

THE EXERCISER IS NOW SET. ALL FIVE RED LED'S WILL FLASH FOR 10 SECONDS

THEN THE UNIT WILL START, RUN THROUGH THE EXERCISE CYCLE AND SHUTDOWN.

0

If DC power to the control board is lost, the weekly exercise setting will be lost. This is indicated by all five red LEDs continually flashing. In this state the generator will still start and run in MANUAL mode, or automatically start and run if utility is lost while in AUTO mode, but it will not perform a weekly exercise cycle.

If a failure occurs while running in this mode, the five red LEDs will stop flashing, the individual fault LED will turn on and the engine will shut down. Once the AUTO/OFF/MANUAL switch has been switched to OFF, the individual fault LED will turn OFF and the five red LEDs will begin flashing to show exercise has still not been set.

3.6WEEKLY EXERCISE CYCLE

The engine control board will start and run the gen- erator once every seven days for approximately 12 minutes. If utility should fail during this exercise period, the engine control board will transfer the load to the generator output and continue to run until util- ity returns.

On the day, and at the time of day chosen for the gen- erator to exercise, set the weekly exercise cycle as fol- lows:

17

Page 19
Image 19
Generac 005030-0, 005028-0, 005031-0 Manual Retransfer And Shutdown, Automatic Operation, Weekly Exercise Cycle