2.4HOW TO USE THE GENERATOR

If there are any problems operating the generator, please call the generator helpline at 1-888-436-3722.

2.4.1 GROUNDING THE GENERATOR

The National Electrical Code requires that the frame and external electrically conductive parts of this generator be properly connected to an approved earth ground (Figure 14). Local electrical codes may also require proper grounding of the unit. For that purpose, generally, connecting a No. 10 AWG (American Wire Gauge) stranded copper wire to the grounding wing nut and to an earth-driven copper or brass grounding rod (electrode) provides adequate protection against electrical shock. However, local codes may vary widely. Consult with a local electrician for grounding requirements in the area.

Figure 14 - Grounding the Generator

Generator Ground Lug

Proper grounding of the generator will help prevent electrical shock in the event of a ground fault condition in the generator or in connected electrical devices. Proper grounding also helps dissipate static electricity, which often builds up in ungrounded devices.

2.4.2 CONNECTING ELECTRICAL LOADS

DO NOT connect 240 Volt loads to 120 Volt receptacles. DO NOT connect 3-phase loads to the generator. DO NOT connect 50 Hz loads to the generator.

Let engine stabilize and warm up for a few minutes after starting.

Plug in and turn on the desired 120 or 240 Volt AC, single phase, 60 Hz electrical loads.

Add up the rated watts (or amps) of all loads to be connected at one time. This total should not be greater than (a) the rated wattage/ amperage capacity of the generator or (b) circuit breaker rating of the receptacle supplying the power. See "Don't Overload the Generator" below.

Operation

2.5DON’T OVERLOAD THE GENERATOR

Overloading a generator in excess of its rated wattage capacity can result in damage to the generator and to connected electrical devices. Observe the following to prevent overloading the unit:

Add up the total wattage of all electrical devices to be connected at one time. This total should NOT be greater than the generator's wattage capacity.

The rated wattage of lights can be taken from light bulbs. The rated wattage of tools, appliances and motors can usually be found on a data label or decal affixed to the device.

If the appliance, tool or motor does not give wattage, multiply volts times ampere rating to determine watts (volts x amps = watts).

Some electric motors, such as induction types, require about three times more watts of power for starting than for running. This surge of power lasts only a few seconds when starting such motors. Make sure to allow for high starting wattage when selecting electrical devices to connect to the generator:

1.Figure the watts needed to start the largest motor.

2.Add to that figure the running watts of all other connected loads.

The Wattage Reference Guide is provided to assist in determining how many items the generator can operate at one time.

NOTE:

All figures are approximate. See data label on appliance for wattage requirements.

2.6WATTAGE REFERENCE GUIDE

Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Running Watts *Air Conditioner (12,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . . . 1700 *Air Conditioner (24,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . . . 3800 *Air Conditioner (40,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . . . 6000 Battery Charger (20 Amp). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500 Belt Sander (3") . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000 Chain Saw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200 Circular Saw (6-1/2") . . . . . . . . . . . . . . . . . . . . . . . . . . .800 to 1000 *Clothes Dryer (Electric) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5750 *Clothes Dryer (Gas) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 700 *Clothes Washer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1150 Coffee Maker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1750 *Compressor (1 HP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000 *Compressor (3/4 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1800 *Compressor (1/2 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1400 Curling Iron. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 700 *Dehumidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 650 Disc Sander (9") . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200 Edge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500 Electric Blanket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400 Electric Nail Gun . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200 Electric Range (per element) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1500 Electric Skillet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1250 *Freezer . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..700 *Furnace Fan (3/5 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 875 *Garage Door Opener . . . . . . . . . . . . . . . . . . . . . . . . . . . .500 to 750 Hair Dryer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200 Hand Drill . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250 to 1100 Hedge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 450 Impact Wrench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500 Iron. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200 *Jet Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 800

9

Page 11
Image 11
Generac 005735-0 HOW to USE the Generator, Wattage Reference Guide, Grounding the Generator, Connecting Electrical Loads

005735-0, 005734-0 specifications

Generac 005735-0 and 005734-0 are high-performance energy solutions designed for residential and light commercial use, offering reliable power backup in various situations. Each model boasts distinct features and technologies that set them apart in the energy market.

The Generac 005735-0 is a 22 kW air-cooled automatic standby generator, engineered to deliver robust performance in the face of power outages. It is especially prized for its advanced Quiet-Test mode, which allows the generator to run at a lower speed for a five- or twelve-minute test, significantly reducing noise levels during routine checks. This feature makes it an excellent choice for neighborhoods with noise restrictions.

Designed with durability in mind, the 005735-0 utilizes a corrosion-resistant aluminum enclosure, ensuring longevity even in harsh weather conditions. Equipped with Generac's G-Flex technology, this model can operate efficiently while providing a steady power supply to essential appliances and systems like HVAC, refrigerators, and lights.

On the other hand, the Generac 005734-0 model features similar specifications but may serve a different market need with slight variations in design. Often marketed for slightly lower power requirements, this model provides a dependable 18 kW output.

Both generators incorporate a robust mobile link monitoring capability, allowing users to check the status and statistics of their generator remotely via a smartphone app. This feature adds a layer of convenience and peace of mind, allowing homeowners to monitor their systems from anywhere.

In terms of installation, these models are straightforward to set up, compatible with existing natural gas or liquid propane systems. They are also supported by Generac's extensive network of authorized installers, making the purchasing and installation process seamless for consumers.

Furthermore, both models come with a five-year limited warranty, affirming Generac's confidence in their reliability and durability. With the ability to provide instant power restoration during outages, the Generac 005735-0 and 005734-0 are ideal options for those prioritizing convenience and peace of mind in their homes.

Overall, these generators embody Generac's commitment to quality, innovation, and user-friendly technology, making them trusted choices for backup power solutions.