Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 2.6ADDITIONAL GENERATOR FEATURES, Overspeed

Models: 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 04077-01, 04109-1, 04079-1, 00789-1, 00844-1

1 32
Download 32 pages 42.29 Kb
Page 23
Image 23
2.5.3.1 Approximate Crank Cycle Times

Section 2 — Operation

2.5.3.1 Approximate Crank Cycle Times

15 seconds ON

15 seconds OFF

7 seconds ON

7 seconds OFF

Repeat for 45 seconds Approximately 90 seconds total

Guardian Air-cooled Generators

2.Remote/Common Alarm – This allows for an alarm, light, horn, etc., to activate when any fault has occurred. Lines #210 (common) and #211 (normally open) provide a “closure” on common fault, which can be used for 120 volts, 10 amps maximum. See Figure 2.5.

3.Remote Not Auto – The generator will not auto- matically start during a utility failure.

2.5.4 OVERSPEED

This feature protects the generator from damage by shutting it down if it happens to run faster than the pre- set limit. This protection also prevents the generator from supplying an output that could potentially damage appliances connected to the generator circuit. The over- speed feature will activate as follows:

1.If the generator runs at 72 Hertz for five seconds, the generator will shut down.

2.If the generator reaches 75 Hertz, it will shut down instantly.

2.6ADDITIONAL GENERATOR FEATURES

2.6.1 6 KW, 8 KW AND 10 KW UNITS (NON-SA)

The standard 6 kW, 8 kW and 10 kW air-cooled Guardians offer additional features that are not factory preset:

1.Remote Start – This allows for remote starting of the generator by means of the #183 (common) and #178 (normally open) lines with the Auto/Off/Manual switch set to AUTO. Closure of the circuit starts the unit; opening of the circuit stops the unit. See Figure 2.5.

NOTE:

This function will work ONLY with the unit in the AUTO mode.

Figure 2.5 – Remote Start/Alarm Options

2.6.2 SOUND ATTENUATED UNITS

Model 00844 of the sound attenuated air-cooled Guardians offers additional features that are not factory preset (see Figure 2.6):

1.Remote Start – This allows for remote starting of the generator by means of the #183 and #178 lines with the Auto/Off/Manual switch set to AUTO.

2.Engine Run Signal – The engine run signal is con- trolled by the #14 line. The “volt free” engine run signal relay closes when the #14 line is “hot.”

3.Automatic Transfer Switch (ATS) in Emergency – For this to be active, a microswitch on the transfer switch sends a signal along the #231 line to close the “volt free” contact relay.

4.Shutdown Fault – This signal is controlled by the main printed circuit board along the #229 line. When a common fault occurs (low oil pressure, high temperature, overspeed, overcrank), the control board will send a signal along the #229 line to close the "volt free" contact relay.

Figure 2.6 – Remote Alarms

–Type 14 AWG wire is recommended.

–These options should be wired to the unit by a qualified electrician or Generac/Guardian Authorized Dealer.

Generac® Power Systems, Inc. 21

Page 23
Image 23
Generac 04077-1, 04109-1, 04079-1, 00789-1, 00844-1 manual 2.6ADDITIONAL GENERATOR FEATURES, Approximate Crank Cycle Times