Section 4 — Maintenance

Carrier Liquid-cooled 15 kW Generators

‹ 4.4.2 BATTERY FLUID

 

‹ 4.5.7 INSPECT EXHAUST SYSTEM

Check battery electrolyte fluid at least once a month. Fluid should cover separators in all battery cells. If fluid level is low, add distilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.

Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.

‹4.4.3 ENGINE COOLANT

Check coolant level in coolant recovery bottle. See Specifications, Section 1.10.

Add recommended coolant mixture as necessary.

Periodically remove radiator pressure cap to make sure the coolant recovery system is functioning properly. Coolant should be at bottom of radiator filler neck. If coolant level is low, inspect gasket in radiator pressure cap. Replace cap, if necessary. To have pressure cap tested, contact a dealer. Inspect cooling system and coolant recovery sys- tem for leaks.

4.5MAINTENANCE OWNER/ OPERATOR CAN PERFORM

‹4.5.1 CHECK ENGINE OIL LEVEL

Refer to “Checking Fluid Levels” in Section 4.4.

‹4.5.2 CHECK BATTERY

Check battery fluid level each week as outlined under “Check Fluid Levels”.

Check battery cables for condition, tightness, cor- rosion or damage. Clean, tighten or replace as necessary.

‹4.5.3 EXERCISE SYSTEM

Start the generator engine at least once every seven days and let it run at least 20 minutes. See Section 3.5, “Weekly Exercise Cycle”.

‹4.5.4 INSPECT COOLING SYSTEM

Inspect engine cooling system at least once each month.

Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.

Check hose clamps for tightness.

‹4.5.5 CHECK ENGINE COOLANT LEVEL

See “Checking Fluid Levels” in Section 4.4.

‹4.5.6 PERFORM VISUAL INSPECTION

Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.

‹4.5.8 CHECK FAN BELT

Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt.

Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 3/4 inch. Adjust belt tension as required.

‹4.5.9 INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

DANGER

Do not attempt to adjust the governor. Only

!qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incorrect frequency and/or voltage. Only quali- fied service technicians should adjust the gov- erned speed.

‹4.5.10 CHANGING ENGINE OIL

Refer to maintenance performed by authorized service facilities for engine oil and filter change frequencies.

Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows:

1.Remove OIL DRAIN HOSE from its retaining clip.

2.Loosen and remove OIL DRAIN HOSE CAP. Drain oil completely into suitable container.

3.When all oil has drained, install and tighten OIL DRAIN HOSE CAP, and re-install into its retaining clip.

4.Turn OIL FILTER (Figure 4.2) counterclockwise and remove. Dispose of old filter.

5.Apply light coating of new engine oil to seal of new oil filter. Install FILTER and tighten by hand only.

DO NOT OVERTIGHTEN.

6.Remove OIL FILL CAP. Add recommended oil (see

SPECIFICATIONS). DO NOT FILL ABOVE THE DIPSTICK “FULL” MARK. Crankcase oil capacity is 4.0 U.S. quarts (3.8 liters).

Carrier 15

Page 17
Image 17
Generac ASPAS1CCL015 ‹ 4.4.2 Battery Fluid ‹ 4.5.7 Inspect Exhaust System, ‹ 4.4.3 Engine Coolant, ‹ 4.5.2 Check Battery

ASPAS1CCL015 specifications

The Generac ASPAS1CCL015 is a cutting-edge automatic standby generator that provides reliable backup power in the event of an electrical outage. Designed with innovative technology and robust features, it ensures that homes and businesses can maintain essential operations without interruptions, enhancing peace of mind and safety during unforeseen power disruptions.

One of the standout features of the Generac ASPAS1CCL015 is its powerful engine, designed to produce up to 15 kilowatts of electricity. This makes it suitable for a wide range of applications, from residential homes to small commercial establishments. The generator operates on propane or natural gas, providing flexibility in fuel options based on user preferences or availability in their region.

Incorporating advanced technologies, the ASPAS1CCL015 is equipped with an automatic transfer switch (ATS). This feature allows the generator to automatically detect power outages and start up within seconds, ensuring that homes remain powered without a manual start. The ATS also reassesses whether the utility power has restored, allowing for a smooth transition back to grid power when available.

The unit is designed to be both quiet and efficient, featuring a low-emission engine that meets stringent environmental standards. This is an increasingly important consideration for many users concerned about eco-friendliness. Its noise-reduction technology ensures that operation is not disruptive, allowing users to run the generator during night hours without disturbing the peace.

In terms of user-friendly features, the Generac ASPAS1CCL015 is equipped with an intuitive digital control panel. Users can easily monitor the generator's status, run diagnostic checks, and access maintenance reminders. This enhances the overall user experience and promotes proactive care of the equipment.

Durability is another hallmark of the ASPAS1CCL015. Constructed with corrosion-resistant materials, the generator can withstand various weather conditions, making it a reliable option for outdoor settings. Its compact design allows for easy installation, whether in a garage, basement, or an external concrete pad.

Overall, the Generac ASPAS1CCL015 combines reliability, advanced technology, and user-friendly features to deliver a dependable electricity solution. Its capability to seamlessly transition between power sources, coupled with the sustainable operation, positions it as an excellent choice for those looking to safeguard their homes or businesses against power outages.