‹1.10.2 ENGINE SPECIFICATIONS

Section 1 — General Information

Carrier Liquid-cooled 15 kW Generators

‹1.10.2 ENGINE SPECIFICATIONS

Make

Mitsubishi

Displacement

92 inches3 (1.5 liters)

Cylinder Arrangement

4, in-line

Valve Arrangement

Overhead Cam

Firing Order

1-3-4-2

Number of Main Bearings

5

Compression Ratio

9 to 1

No. of Teeth on Flywheel

104

Ignition Timing

 

at 1800 rpm

35 degrees BTDC

Spark Plug Gap

0.020-0.025 inch

Recommended Spark Plugs

 

Champion

RN11YC4

Oil Pressure

30-50 psi

Crankcase Oil Capacity

3.0 U.S. quarts (2.8 liters)

Recommended Engine Oil

SAE 15W-40

Type of Cooling System

Pressurized, closed recovery

Cooling Fan

Pusher Type

Cooling System Capacity

2 U.S. gallons (7.6 liters)

Recommended Coolant

Use a 50-50 mixture of

 

ethylene glycol base.

1.11 FUEL CONSUMPTION

15 kW Models

Using Natural Gas

........................................277 cu. ft. per hour

Using LP Gas

110 cubic ft.(3.1 gal.) per hour

 

NOTE:

Fuel consumption is given at rated maximum con- tinuous power output when using natural gas rated at 1000 Btu per cubic foot and LP gas rated 2520 Btu per cubic foot. Actual fuel consumption obtained may vary depending on such variables as applied load, ambient temperature, engine condi- tions and other environmental factors.

Fuel pressure for a natural gas set up should be five inches to 14 inches of water column (0.18 to 0.5 psi) at all load ranges.

Fuel pressure for an LP vapor set up should be 11 inches to 14 inches of water column (0.4 to 0.5 psi) at all load ranges.

1.12RECONFIGURING THE FUEL SYSTEM

NOTE:

All models are configured for natural gas from the factory.

To reconfigure the fuel system from NG to LP, follow these steps:

1.Turn the main gas supply off.

2.Remove the carburetor fuel hose from the outlet port (Port 1) of the demand regulator (Figure 1.8).

3.Remove the brass hose fitting from the outlet port (Port 1) of the demand regulator.

4.Remove pipe plug from Port 2.

5.Install brass hose fitting into Port 2.

6.Install pipe plug into Port 1.

7.Connect carburetor gas hose to brass fitting.

8.Tighten all clamps and plugs.

9.Make sure fuel supply is of the proper pressure and type for configuration.

10.Reverse the procedure to convert back to natural gas.

Figure 1.8 — Reconfigure the Fuel System

 

Port 1

 

Port 2

 

FUEL HOSE

FUEL HOSE

 

PLUG

BRASS HOSE

BRASS HOSE

PLUG

FITTING

FITTING

 

 

 

OUT

OUT

 

 

PORT 1

PORT 2

 

 

HOUSING

HOUSING

 

 

PORTS

PORTS

 

 

 

 

NG FUEL SYSTEM

LP FUEL SYSTEM

NOTE:

Port 1 is for NG only and Port 2 is for LP vapor only. No provision for simultaneous fuels has been made.

1.11 FUEL CONSUMPTION1.12RECONFIGURING THE FUEL SYSTEM DANGER

Serious injury or damage may occur if not con-

!figured properly. Please consult a dealer with any questions.

1.13 TORQUE SPECIFICATIONS

Cylinder Head

15 (+ 90° + 90°) ft.lb.

Intake Manifold

13 ft.lb.

Exhaust Manifold

13 ft.lb.