Section 2 — Installation

Guardian Liquid-cooled 40 kW Generator

2.7BATTERY INSTALLATION

DANGER

Standby generators installed with automatic trans- ! fer switches will crank and start automatically

when NORMAL (UTILITY) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to personnel, do not connect battery cables until the NORMAL source voltage at the transfer switch is correct and the system is ready to be placed into operation.

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the bat- tery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely caustic ! sulfuric acid solution that can cause severe burns.

Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

Do not dispose of the battery in a fire. The battery is capable of exploding.

Do not open or mutilate the battery. Released ! electrolyte can be toxic and harmful to the skin

and eyes.

The battery represents a risk of high short circuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.

‹2.7.1 VENTED BATTERIES

The electrolyte is a dilute sulfuric acid that is

!harmful to the skin and eyes. It is electrically con- ductive and corrosive. The following procedures are to be observed:

Wear full eye protection and protective clothing,

Where electrolyte contacts the skin, wash it off immediately with water,

Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical atten- tion, and

Spilled electrolyte is to be washed down with an acid- neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbonate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

Lead acid batteries present a risk of fire because they generate hydrogen gas. The following proce- dures are to be followed:

DO NOT SMOKE when near batteries,

DO NOT cause flame or spark in battery area, and

Discharge static electricity from body before touching batteries by first touching a grounded metal surface.

Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.

For recommended batteries, see Section 4.5, “Battery Maintenance”. All batteries must be at 100 percent state- of-charge before they are installed on the generator.

When using maintenance-free batteries, it is not neces- sary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals spec- ified in Section 4, “Maintenance.” A negative ground sys- tem is used. Battery connections are shown on the wiring diagrams. Make sure all batteries are correctly connected and terminals are tight. Observe battery polarity when connecting batteries to the generator set.

NOTE:

Damage will result if the battery connections are reversed.

10 Generac® Power Systems, Inc.

Page 12
Image 12
Generac Power Systems 004626-5, 004373-6 owner manual Battery Installation, ‹ 2.7.1 Vented Batteries

004373-6, 004626-5 specifications

Generac Power Systems has established itself as a leader in the field of backup and portable power solutions, and their models 004626-5 and 004373-6 are prime examples of their dedication to innovation and reliability. These models are designed to cater to a variety of power needs, making them essential assets for homeowners and businesses alike.

The 004626-5 is a robust home standby generator, renowned for its powerful performance and automatic transfer switch capabilities. This model features Generac's G-Force engine, which is specifically engineered for high performance and longevity, ensuring that it can handle the demands of powering a home during outages. It boasts a multi-language LCD display that provides real-time system status updates, allowing users to monitor performance with ease. Additionally, the 004626-5 is equipped with an integrated wi-fi system, enabling remote monitoring through the Mobile Link app. This feature gives users the convenience of checking their generator's status from anywhere, ensuring peace of mind.

On the other hand, the 004373-6 is a portable generator designed for versatility and convenience. This model is lightweight and easily transportable, making it ideal for outdoor activities, job sites, or emergency power supply during outages. Powered by a reliable OHV engine, the 004373-6 delivers impressive power output while maintaining fuel efficiency. Its ergonomic design includes a transport handle and never-flat wheels, allowing for easy maneuverability. The model also features Generac’s PowerRush technology, which provides over 50% more starting capacity, making it capable of handling larger appliances with ease.

Both models are designed with safety features in mind. The 004626-5 comes with a durable weather-resistant enclosure, protecting it from the elements, while the 004373-6 includes a low-oil shutdown feature to prevent engine damage.

In summary, Generac Power Systems continues to set the benchmark for reliability and innovation in power solutions with models 004626-5 and 004373-6. With their advanced technologies, user-friendly features, and unparalleled performance, these generators are engineered to provide power when it’s needed most, ensuring a seamless transition during outages and enhancing convenience for users across various settings.