Important Safety Instructions

Guardian Liquid-cooled 40 kW Generator

Inspect the generator regularly, and promptly repair or replace all worn, damaged or defective parts using only factory-approved parts.

Before performing any maintenance on the generator, disconnect its battery cables to prevent accidental start-up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.

Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.

ELECTRICAL HAZARDS

All generators covered by this manual produce dan- gerous electrical voltages and can cause fatal electri- cal shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in operation. Avoid con- tact with bare wires, terminals, connections, etc., while the unit is running. Ensure all appropriate cov- ers, guards and barriers are in place before operating the generator. If work must be done around an oper- ating unit, stand on an insulated, dry surface to reduce shock hazard.

Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.

If people must stand on metal or concrete while installing, operating, servicing, adjusting or repairing this equipment, place insulative mats over a dry wooden platform. Work on the equipment only while standing on such insulative mats.

The National Electrical Code (NEC) requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground and/or grounding rods. This grounding will help prevent dangerous electrical shock that might be caused by a ground fault condition in the generator set or by static electricity. Never disconnect the ground wire.

Wire gauge sizes of electrical wiring, cables and cord sets must be adequate to handle the maximum elec- trical current (ampacity) to which they will be sub- jected to.

Before installing or servicing this (and related) equip- ment, make sure that all power voltage supplies are positively turned off at their source. Failure to do so will result in hazardous and possibly fatal electrical shock.

Connecting this unit to an electrical system normally supplied by an electric utility shall be by means of a transfer switch so as to isolate the generator electric system from the utility electric system while in oper- ation. Failure to isolate the two electric system power sources from each other by such means will result in damage to the generator and may also result in injury or death to utility power workers due to backfeed of electrical energy.

Generators installed with an automatically transfer switch will crank and start automatically when NOR- MAL (UTILITY) source voltage is removed or is below an acceptable preset level. To prevent such automat- ic start-up and possible injury to personnel, disable the generator’s automatic start circuit (battery cables, etc.) before working on or around the unit. Then, place a “Do Not Operate” tag on the generator control panel and on the transfer switch.

In case of accident caused by electric shock, immedi- ately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.

Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.

FIRE HAZARDS

Keep a fire extinguisher near the generator at all times. DO NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insulation. Keep the extinguisher properly charged and be familiar with its use. If there are any questions pertaining to fire extinguishers, consult the local fire department.

EXPLOSION HAZARDS

Properly ventilate any room or building housing the generator to prevent build-up of explosive gas.

Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.

Generac generator sets may operate using one of sev- eral types of fuels. All fuel types are potentially FLAM- MABLE and/or EXPLOSIVE and should be handled with care. Comply with all laws regulating the storage and handling of fuels. Inspect the unit’s fuel system frequently and correct any leaks immediately. Fuel supply lines must be properly installed, purged and leak tested according to applicable fuel-gas codes before placing this equipment into service.

Diesel fuels are highly FLAMMABLE. Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier than air; install leak detectors accordingly.

Generac® Power Systems, Inc. 3

Page 5
Image 5
Generac Power Systems 004373-6, 004626-5 owner manual Electrical Hazards

004373-6, 004626-5 specifications

Generac Power Systems has established itself as a leader in the field of backup and portable power solutions, and their models 004626-5 and 004373-6 are prime examples of their dedication to innovation and reliability. These models are designed to cater to a variety of power needs, making them essential assets for homeowners and businesses alike.

The 004626-5 is a robust home standby generator, renowned for its powerful performance and automatic transfer switch capabilities. This model features Generac's G-Force engine, which is specifically engineered for high performance and longevity, ensuring that it can handle the demands of powering a home during outages. It boasts a multi-language LCD display that provides real-time system status updates, allowing users to monitor performance with ease. Additionally, the 004626-5 is equipped with an integrated wi-fi system, enabling remote monitoring through the Mobile Link app. This feature gives users the convenience of checking their generator's status from anywhere, ensuring peace of mind.

On the other hand, the 004373-6 is a portable generator designed for versatility and convenience. This model is lightweight and easily transportable, making it ideal for outdoor activities, job sites, or emergency power supply during outages. Powered by a reliable OHV engine, the 004373-6 delivers impressive power output while maintaining fuel efficiency. Its ergonomic design includes a transport handle and never-flat wheels, allowing for easy maneuverability. The model also features Generac’s PowerRush technology, which provides over 50% more starting capacity, making it capable of handling larger appliances with ease.

Both models are designed with safety features in mind. The 004626-5 comes with a durable weather-resistant enclosure, protecting it from the elements, while the 004373-6 includes a low-oil shutdown feature to prevent engine damage.

In summary, Generac Power Systems continues to set the benchmark for reliability and innovation in power solutions with models 004626-5 and 004373-6. With their advanced technologies, user-friendly features, and unparalleled performance, these generators are engineered to provide power when it’s needed most, ensuring a seamless transition during outages and enhancing convenience for users across various settings.