Section 4 — Maintenance

Guardian Liquid-cooled 40 kW Generator

Figure 3.2 – Engine Block Heater

OUTLET

NOTE:

If the battery terminals are disconnected or the con- trol panel fuse is removed, the exercise timer needs to be reset for automatic exercise operation.

Figure 3.3 – “Set Exercise” Switch on Control Panel

INLET

Refer to applicable wiring diagram(s) and electrical schematic(s) at the back of this manual for wiring con- nections.

3.6WEEKLY EXERCISE CYCLE

The generator will start and exercise once every seven days. During this weekly exercise, the unit runs for approximately 20 minutes and shuts down. Transfer of loads to generator output does not occur during the exercise unless power is lost during the exercise period.

To select the day of the week and time of day for exer- cising, proceed as follows:

Set the AUTO/OFF/MANUAL switch to OFF.

Set generator’s main circuit breaker to its OFF (or open) position.

Locate the rocker switch on the control panel identi- fied with the words “Set Exercise Time” (Figure 3.3).

Push “Set Exercise Time” switch to the ON position for 20 to 30 seconds and then release. The switch will spring back into its original position when released.

Wait 30 seconds before setting the AUTO/OFF/ MANUAL switch to the AUTO position.

NOTE:

The unit will exercise 20 minutes before it is set. Example: Set – Noon; Exercise – 11:40 a.m.

If you switch the AUTO/OFF/MANUAL switch is

!switched too soon, the engine may start. If engine does start, it will shut down automatically in about two (2) minutes.

Set the generator’s main circuit breaker to its ON (or closed) position.

The generator is now programmed to start and exer- cise every seven days thereafter, on the day and at the time of day the switch was activated.

Place a sign on the generator’s control panel and on the transfer switch that indicates the day and time the generator will be exercising.

14 Generac® Power Systems, Inc.

4.1CHECKING THE ENGINE OIL LEVEL

For oil capacities, see “Specifications,” Section 1.8. For engine oil recommendations, see Section 4.2.1. To check the engine oil level, proceed as follows (Figure 4.1):

1.Remove the dipstick and wipe it dry with a clean cloth.

2.Install the dipstick cap; then, remove it again. The oil level should be at the dipstick “Full” mark. If nec- essary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL” MARK.

3.Install the dipstick.

Figure 4.1 – Oil Dipstick and Fill

￿￿￿￿￿￿￿￿￿￿￿￿

￿￿￿￿￿￿￿￿￿￿￿￿

Never operate the engine with the oil level below

!the “Add” mark on the dipstick. Doing this could damage the engine.

Page 16
Image 16
Generac Power Systems 004626-5, 004373-6 owner manual Weekly Exercise Cycle, Checking the Engine OIL Level

004373-6, 004626-5 specifications

Generac Power Systems has established itself as a leader in the field of backup and portable power solutions, and their models 004626-5 and 004373-6 are prime examples of their dedication to innovation and reliability. These models are designed to cater to a variety of power needs, making them essential assets for homeowners and businesses alike.

The 004626-5 is a robust home standby generator, renowned for its powerful performance and automatic transfer switch capabilities. This model features Generac's G-Force engine, which is specifically engineered for high performance and longevity, ensuring that it can handle the demands of powering a home during outages. It boasts a multi-language LCD display that provides real-time system status updates, allowing users to monitor performance with ease. Additionally, the 004626-5 is equipped with an integrated wi-fi system, enabling remote monitoring through the Mobile Link app. This feature gives users the convenience of checking their generator's status from anywhere, ensuring peace of mind.

On the other hand, the 004373-6 is a portable generator designed for versatility and convenience. This model is lightweight and easily transportable, making it ideal for outdoor activities, job sites, or emergency power supply during outages. Powered by a reliable OHV engine, the 004373-6 delivers impressive power output while maintaining fuel efficiency. Its ergonomic design includes a transport handle and never-flat wheels, allowing for easy maneuverability. The model also features Generac’s PowerRush technology, which provides over 50% more starting capacity, making it capable of handling larger appliances with ease.

Both models are designed with safety features in mind. The 004626-5 comes with a durable weather-resistant enclosure, protecting it from the elements, while the 004373-6 includes a low-oil shutdown feature to prevent engine damage.

In summary, Generac Power Systems continues to set the benchmark for reliability and innovation in power solutions with models 004626-5 and 004373-6. With their advanced technologies, user-friendly features, and unparalleled performance, these generators are engineered to provide power when it’s needed most, ensuring a seamless transition during outages and enhancing convenience for users across various settings.