Section 5 — Troubleshooting

QUIETSOURCELiquid-cooled 30 kW Generators

TROUBLESHOOTING POINTS

PROBLEM

CAUSE

CORRECTION

Engine won’t crank.

1.

15 amp fuse blown.

1.

Replace fuse.

 

2.

Loose or corroded or defective

2.

Tighten, clean or replace

 

 

battery cables.

 

battery cables as necessary.

 

3.

Defective starter contactor.

3.

Replace contactor.

 

4.

Defective starter motor.

4.

Replace starter motor.

 

5.

Dead or Defective Battery.

5.

Remove, change or replace battery.

 

6.

4 amp fuse blown.

6.

Replace fuse.

 

 

 

 

 

Engine cranks, but won't start

1.

Out of fuel.

1.

Replenish fuel.

 

2.

Fuel solenoid (FS) is defective

2.

Replace solenoid.

 

3.

Open Wire #14 from Engine Control

3.

Reconnect wire.

 

 

circuit board.

 

 

 

4.

Spark plugs defective.

4.

Clean, regap or replace plugs.

 

 

 

 

 

Engine starts hard, runs rough.

1.

Flame arrestor (air cleaner) plugged or

1.

Clean or replace as needed.

 

 

damaged.

 

 

 

2.

Plugged fuel line.

2.

Unclog fuel line.

 

3.

Defective spark plugs.

3.

Clean, regap or replace plugs.

 

 

 

 

 

Engine starts, then shuts down.

1.

Engine oil level is low.

1.

Check oil and add oil as needed.

 

2.

Engine is overheated.

2.

Check cooling system for leaks.

 

3.

Defective Low Oil Pressure Switch

3.

Replace switch.

 

4.

Defective Coolant Temperature Switch

4.

Replace switch.

 

5.

Defective Control Module circuit board.

5.

Replace board.

 

6.

Coolant Level is Low.

6.

Repair leak - Add coolant.

 

7.

Defective Low Coolant Level Switch

7.

Replace Switch.

 

 

 

 

 

AUTO/OFF/MANUAL Switch at,

1.

Defective AUTO/OFF/MANUAL switch

1.

Replace switch.

OFF engine continues to run

2.

Open/disconnected wire #15A between

2.

Reconnect/close wire.

 

 

AUTO/OFF/MANUAL switch and Control

 

 

 

 

Module circuit board.

 

 

 

3.

Defective Control Module circuit board

3.

Replace board.

 

 

 

 

 

No AC output from generator.

1.

Check main line circuit breaker.

1.

Reset to ON or CLOSED.

 

2.

Check circuit breaker & fuses.

2.

Reset and replace, if necessary.

 

3.

Transfer switch set to NORMAL position

3.

Set to GENERATOR position.

 

4.

Generator internal failure.

4.

Contact an Authorized Generac

 

 

 

 

facility.

 

5.

Thermal circuit breaker open.

5.

Auto-reset - Wait five minutes and

 

 

 

 

attempt restart.

Generac® Power Systems, Inc. 23

Page 25
Image 25
Generac Power Systems 004917-2 owner manual Troubleshooting Points, Problem Cause Correction

004917-2 specifications

Generac Power Systems 004917-2 is a noteworthy addition to the realm of home power solutions, designed to provide reliable backup power during outages and enhance energy management for residential users. This model is recognized for its robust engineering and advanced features, making it a preferred choice for homeowners seeking uninterrupted power supply.

One of the standout characteristics of the 004917-2 is its quiet operation, achieved through innovative noise-reduction technology. This feature ensures that users can enjoy a peaceful environment without the disruptive sounds often associated with traditional generators. The unit is designed not only for functionality but also for discretion, seamlessly blending into residential settings.

Built with a powerful engine, the 004917-2 delivers an impressive wattage capacity, ensuring that essential appliances such as refrigerators, lights, and heating systems can function smoothly during power outages. Its automatic transfer switch capability is a significant technological advancement, allowing the generator to detect power loss and activate without user intervention. This means that homeowners can have peace of mind knowing that their critical systems will remain operational when most needed.

Another notable feature of the Generac 004917-2 is its user-friendly control panel, equipped with digital indicators that provide real-time monitoring of the generator's performance. This interface allows users to easily assess power usage, fuel levels, and maintenance schedules, empowering them with the information necessary to manage their energy needs effectively.

Moreover, the 004917-2 is designed for fuel efficiency, incorporating eco-friendly technologies that optimize fuel consumption while delivering high power output. This design not only helps to reduce operational costs but also minimizes the environmental impact.

In terms of durability, the unit boasts a corrosion-resistant exterior that enhances its lifespan, making it suitable for various climates and conditions. Generac's commitment to quality assurance is evident in the rigorous testing that each model undergoes before reaching the consumer market.

In summary, the Generac Power Systems 004917-2 stands out as a reliable and efficient solution for homeowners looking for dependable backup power. With its quiet operation, powerful performance, automatic transfer capabilities, user-friendly interface, fuel efficiency, and robust construction, it meets the demands of modern energy use while offering peace of mind during unexpected outages.