Generac Power Systems 004917-3 Specifications, Fuel Consumption, ‹1.10.2 ENGINE SPECIFICATIONS

Models: 004917-3

1 48
Download 48 pages 36.72 Kb
Page 9
Image 9
1.10 SPECIFICATIONS

Section 1 — General Information

QUIETSOURCELiquid-cooled 30 kW Generators

1.10 SPECIFICATIONS

NOTE:

‹ 1.10.1 GENERATOR SPECIFICATIONS

 

 

Single-phase

 

 

Model

4917-3

 

 

Rated Max. Cont.

27 (NG), 30 (LP)

 

 

AC Power Output (kW)

 

 

 

Rated voltage (volts)

120/240

 

 

No. of Rotor Poles

4

 

 

Driven Speed of Rotor

1800

 

 

Rotor Excitation System

Direct excited brush type

 

 

Type of Stator

4 Wire

 

 

Rotor/Stator Insulation

Class F/H

 

Fuel consumption is given at rated maximum con- tinuous power output when using natural gas rated at 1000 Btu per cubic foot. LP gas is rated at 2520 Btu per cubic foot. Actual fuel consumption obtained may vary depending on such variables as applied load, ambient temperature, engine condi- tions and other environmental factors.

Fuel pressure for a natural gas set up should be five inches to 14 inches of water column (0.18 to 0.5 psi) at all load ranges.

Fuel pressure for an LP vapor set up should be 11 inches to 14 inches of water column (0.4 to 0.5 psi) at all load ranges.

‹1.10.2 ENGINE SPECIFICATIONS

Make

Ford

Displacement

3.0 liters

Cylinder Arrangement

V-6

Valve Arrangement

Overhead Valve

Firing Order

1-4-2-5-3-6

Number of Main Bearings

4

Compression Ratio

9.3 to 1

No. of Teeth on Flywheel

164

Ignition Timing at 1800 rpm

30 degrees BTDC

Spark Plug Gap

0.042-0.046 inch

Recommended Spark Plugs

 

Motor Craft

AG, SF 32PGM

Oil Pressure

40-50 psi

Crankcase Oil Capacity

5.0 U.S. quarts (4.7 liters)

Recommended Engine Oil

SAE 5W-20

Type of Cooling System

Pressurized, closed recovery

Cooling Fan

Pusher Type

Cooling System Capacity

3.0 U.S. gallons (11.4 liters)

Recommended Coolant

Use a 50-50 mixture of

 

ethylene glycol base

 

and de-ionized water.

1.11 FUEL CONSUMPTION

Natural Gas:

 

% of Load

25%

50%

75%

100%

 

m3/hr

3.1

5.9

8.5

11.0

 

ft3/hr

110.3

209.0

299.5

387.0

LP Vapor:

 

 

 

 

 

% of Load

25%

50%

75%

100%

 

m3/hr

1.3

2.4

3.5

4.5

 

ft3/hr

45.6

86.4

123.8

160.0

1.12RECONFIGURING THE FUEL SYSTEM

NOTE:

All models are configured for natural gas from the factory.

To reconfigure the fuel system from NG to LP vapor, follow these steps:

1.Turn the main gas supply off.

2.Remove the carburetor fuel hose from the outlet port (Port 1) of the demand regulator (Figure 1.8).

3.Remove the brass hose fitting from the outlet port (Port 1) of the demand regulator.

4.Remove pipe plug from Port 2.

5.Install brass hose fitting into Port 2.

6.Install pipe plug into Port 1.

7.Connect carburetor gas hose to brass fitting.

8.Tighten all clamps and plugs.

9.Make sure fuel supply is of the proper pressure and type for configuration.

10.Reverse the procedure to convert back to natural gas.

Figure 1.8 — Reconfigure the Fuel System

 

Port 1

 

Port 2

 

FUEL HOSE

FUEL HOSE

 

PLUG

BRASS HOSE

BRASS HOSE

PLUG

FITTING

FITTING

 

 

OUT

OUT

 

 

PORT 1

PORT 2

 

 

HOUSING

HOUSING

 

 

PORTS

PORTS

 

 

 

 

NG FUEL SYSTEM

LP FUEL SYSTEM

Generac® Power Systems, Inc. 7

Page 9
Image 9
Generac Power Systems 004917-3 owner manual Specifications, Fuel Consumption, 1.12RECONFIGURING THE FUEL SYSTEM