Standby Generator Sets

Maintenance

MAINTENANCE PERFORMED BY SERVICE FACILITIES

Before working on the generator, ensure the fol- lowing:

The AUTO/OFF/MANUAL switch is in the OFF position.

The 15A fuse has been removed from the con- trol box.

The 120VAC supply to the battery charger is switched OFF.

‹EVERY THREE MONTHS

1.Check battery condition.

2.Inspect and test fuel system.

3.Check transfer switch.

4.Inspect exhaust system.

5.Check engine ignition system.

6.Check fan belts.

‹ONCE EVERY SIX MONTHS

1.Test Engine Safety Devices (low oil pressure, low coolant level, high coolant temperature).

‹ONCE ANNUALLY

1.Test engine governor; adjust or repair, if needed.

2.Clean, inspect generator.

3.Flush cooling system.

COOLING SYSTEM

Air intake and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down. (See the installation diagram.)

The exhaust system parts from this product get extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL SYSTEM

Engine cranking, start up and running are controlled by a solid state Engine Controller circuit board. Battery voltage is delivered to that circuit board via a 15 amp fuse. These overcurrent protection devices will open if the circuit is overloaded.

If a circuit breaker opens or a fuse element melts, find the cause of the overload before resetting the circuit breaker or replacing the fuse.

‹FIRST 30 OPERATING HOURS

1. Change engine "break-in" oil and filter.

‹FIRST 100 OPERATING HOURS

1.Change engine oil and oil filter. After initial change, service engine oil and filter at 100 operat- ing hours or six months, whichever comes first.

2.Retorque cylinder head.

3.Retorque intake and exhaust manifold.

‹EVERY 500 OPERATING HOURS

1.Service air cleaner.

2.Check starter.

3.Check engine DC alternator.

CHECKING FLUID LEVELS

‹CHECK ENGINE OIL

Check engine crankcase oil level (Figure 10.1) at least every 20 hours of operation, or prior to use.

Remove oil dipstick and wipe dry with a clean, lint- free cloth.

Install oil dipstick, then remove again.

Oil should be between FULL and ADD marks.

If oil level is below the dipstick ADD mark, remove oil fill cap-. Add the recommended oil to bring oil level up to the FULL mark. DO NOT FILL ABOVE THE “FULL” MARK. See “Engine Oil Recommen- dations” for recommended oils.

‹EVERY 800 OPERATING HOURS

1.Retorque cylinder head.

2.Retorque intake and exhaust manifold.

3.Check engine compression.

4.Check valve clearance.

10-1

06/07 D .Rev Maint011

Page 16
Image 16
Generac Power Systems 005324-1, 005325-1 owner manual Maintenance Performed by Service Facilities, Cooling System

005324-1, 005325-1 specifications

Generac Power Systems has long been a leader in backup power solutions, and their Generac Power Systems 005324-1 and 005325-1 models epitomize the brand's commitment to reliability and innovation. These advanced systems are engineered to provide seamless power during outages, ensuring that homes and businesses remain operational even during prolonged power disruptions.

The Generac 005324-1 model is designed for maximum efficiency and performance, boasting a robust 22 kW output, which can power essential appliances, HVAC systems, and more. Its tri-fuel capability allows it to run on natural gas, propane, or gasoline, offering flexibility and convenience depending on the availability and user preferences. This versatility is a significant advantage, as it ensures that users can maintain their power supply regardless of fuel availability during emergencies.

On the other hand, the Generac 005325-1 model is slightly more powerful, delivering 24 kW of output. This model is particularly suited for larger homes or facilities that require additional capacity to support multiple high-demand appliances. Similar to the 005324-1, the 005325-1 features the same tri-fuel capability, allowing users to choose their preferred fuel source.

Both models are outfitted with Generac’s innovative G-Force engine, designed for high performance and long-lasting durability. This engine is engineered specifically for generator use, ensuring that it provides reliable power without the wear and tear associated with typical automotive engines. The G-Force engine is backed by a comprehensive 5-year limited warranty, demonstrating Generac’s commitment to product quality and customer assurance.

In addition to their robust performance, both generator models come equipped with Smart Management Modules, which optimize power usage by allowing homeowners to manage their energy consumption more effectively. This feature prevents overloading the generator, ensuring an uninterrupted power supply even when multiple devices are in use.

Furthermore, the intuitive mobile app allows users to monitor their generator’s performance, receive real-time alerts, and schedule maintenance, enhancing user convenience. Generac has also integrated a quiet operation feature, making these models some of the quieter alternatives in the market, which is particularly important for residential areas.

In summary, the Generac Power Systems 005324-1 and 005325-1 models are powerful, versatile, and reliable generators, perfect for anyone in need of consistent backup power during outages. Their unique features, advanced technologies, and user-friendly characteristics make them a smart investment for long-term peace of mind.