Humidity Control

Humidity Control

When using a Humidistat (normally closed), cut jumper PJ6 on the control board. The Humidistat will only affect cooling airflow by adjusting the Airflow to 85%.

Two Stage Heating

When using staged electric heat, cut jumper PJ4 on the control board.

Thermostat Wiring

Use thermostat wiring diagram Figures 10 thru 13 and those provided with the thermostat when making these connections.

NOTE: DO NOT USE THESE DIAGRAMS FOR AEPT MODELS. SEE SUPPLEMENTAL INSTALLATION AND OPERATING INSTRUCTIONS FOR AEPT MODELS.

ROOM THERMOSTAT

W Y G R

R

G

Two Stage HeatingW

Y Thermostat Wiring

CONTACTOR TO CONDENSING

COIL UNIT 24V. CONNECTIONS #18 GA. 2 WIRESAR UNIT

#18 GA. 4 WIRES WITH COOLING 3 WIRES WITHOUT

AR UNIT

RED

GREEN

WHITE

BLUE

Figure 10 - Low Voltage Wiring Diagram for Cooling Unit with optional heat kit 10KW and below

ROOM THERMOSTAT

 

W2 W Y G R

AR UNIT

#18 GA. 4 WIRE WITH

 

 

COOLING 3 WIRE WITHOUT

R

RED

 

Y

 

 

 

 

G

GREEN

 

OUTDOOR

 

 

 

 

 

THERMOSTAT

W

WHITE

 

(OPTIONAL)

 

 

 

#18 GA. 2 WIRES

 

 

CONTACTOR CONDENSING

 

BROWN

 

 

COIL

UNIT 24V. CONNECTIONS

 

 

#18 GA. 2 WIRES

BLUE

 

Figure 11 - Low Voltage Wiring Diagram for Cooling Unit with optional heat kit 15KW and above

IO-230F

11

08/04

 

 

Page 11
Image 11
Goodman Mfg AEPT, ARPT, ARPF operating instructions Ar Unit, Humidity Control, Two Stage Heating, Thermostat Wiring