=.96 (230 Supply Volts) =.92 (220 Supply Volts) =.87 (208 Supply Volts)

CFM

 

 

HEAT KIT NOMINAL kW

 

 

3

5

6

8

10

15

 

20

21

 

 

600

16

25

32

37

 

 

 

 

 

800

12

19

24

38

38

 

 

 

 

1000

10

15

19

22

30

46

 

 

 

1200

8

13

16

19

25

38

 

51

56

1400

7

11

14

16

22

33

 

43

48

1600

6

9

12

14

19

28

 

38

42

1800

5

8

11

12

17

25

 

34

37

2000

5

8

10

11

15

23

 

30

34

Table 4

208/1/60 Supply Voltage - Temperature Rise Table °F

NOTE: For installations not indicated above the following formula is to be used:

TR = (kW x 3412) x (Voltage Correction) x 1.08 / CFM

Where: TR

= Temperature Rise

kW

= Heater Kit Actual kW

3412 = Btu per kW Voltage Correction

1.08= Constant

CFM = Measured Airflow

NOTE: The Temperature Rise Tables can also be used to determine the air handler airflow delivery. When using these tables for this purpose set the room thermostat to maximum heat and allow the system to reach steady state conditions. Insert two thermometers, one in the return air and one in the supply air. The temperature rise is the supply air temperature minus the room air temperature.

Use HKR specification sheets to determine the HKR avail- able for a given air handler.

HKR Installation

Follow instructions listed in Installation and Operating Instruc- tions shipped with the heat kit.

Electrical Supply Wire and MOP

FIRE HAZARD!

To avoid the risk of property damage, personal injury or fire, use only copper conductors.

HIGH VOLTAGE!

Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.

HIGH VOLTAGE!

To avoid property damage, personal injury or death due to electrical shock, this unit MUST have an uninterrupted, unbroken electrical ground. The electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel.

Other methods of grounding are permitted if performed in accordance with the National Electric Code (NEC)/American National Standards Institute (ANSI)/National Fire Protection Association (NFPA) 70 and local/state codes. In Canada, electrical grounding is to be in accordance with the Canadian Electric Code (CSA) C22.1.

Building Electrical Service Inspection

This unit is designed for single-phase electrical supply. DO NOT OPERATE ON A THREE-PHASE POWER SUPPLY. Measure the power supply to the unit. The supply voltage must be in agreement with the unit nameplate power require- ments and within the range shown in Table 5.

Nominal Input

Minimum Voltage

Maximum Voltage

 

 

 

208/240

187

253

 

Table 5

 

Wire Sizing

Wire size is important to the operation of your equipment. Use the following check list when selecting the appropriate wire size for your unit.

Wire size must carry the Minimum Circuit Ampac- ity (MCA).

Refer to the NEC (USA) or CSA (Canada) for wire siz- ing. The unit MCA for the air handler and the optional electric heat kit can be found on the unit Series and Rating Plate.

Wire size allows for no more than a 2% voltage drop from the building breaker/fuse panel to the unit.

Refer to the latest edition of the National Electric Code or in Canada the Canadian Electric Code when deter- mining the correct wire size. The following table shows the current carrying capabilities for copper conductors rated at 75oC with a 2% voltage drop. Use Table 6 to determine the voltage drop per foot of various conduc- tors.

Maximum Allowable Length in Feet

to Limit Voltage Drop to 2%*

Wire Size

 

Minimum Circuit Ampacity (MCA)

 

(AWG)

 

 

 

 

 

 

 

 

10

15

20

25

30

35

40

45

 

 

 

 

 

 

 

 

 

 

14

75

50

37

NR

NR

NR

NR

NR

12

118

79

59

47

NR

NR

NR

NR

10

188

125

95

75

63

54

NR

NR

8

301

201

150

120

100

86

75

68

6

471

314

235

188

157

134

118

110

*Based on NEC 1996

Table 6

5

Page 5
Image 5
Goodman Mfg ASPF, ATUF, ARUF, ADPF installation manual HKR Installation, Electrical Supply Wire and MOP

ATUF, ADPF, ASPF, ARUF specifications

Goodman Manufacturing is synonymous with quality and reliability in the HVAC industry, offering a wide range of air handling units, including the ARUF, ASPF, ADPF, and ATUF series. These products showcase advanced technologies while providing cost-effective solutions for residential and commercial applications.

The ARUF series is designed specifically for reliable indoor air management. These air handlers are known for their high-efficiency performance and compact design, making them suitable for tight spaces. They feature an insulated cabinet that minimizes noise and energy loss, ensuring a quieter operation and increased comfort. The ARUF units also have a multi-speed blower motor, which provides improved airflow and better temperature control, enhancing overall system efficiency.

The ASPF series stands out with its variable-speed motor technology. This innovation allows for precise airflow adjustments, adapting seamlessly to changing thermal loads within the space. Such adaptability not only improves comfort levels but also leads to energy savings by optimizing performance during varying usage periods. Additionally, the ASPF air handlers are designed for easy installation, incorporating lightweight components and a versatile design that accommodates different configurations and applications.

Meanwhile, the ADPF series is highly regarded for its durability and performance in moisture-rich environments. Engineered with a robust housing, the ADPF units offer increased corrosion resistance, making them ideal for locations susceptible to humidity. The units come equipped with enhanced filtration capabilities, ensuring improved indoor air quality by capturing dust, pet dander, and other allergens effectively.

Lastly, the ATUF series combines advanced technology with user-friendly features. These units feature a high-efficiency air filter and a low-profile design, perfect for a variety of applications. The ATUF air handlers come equipped with integrated control systems that allow users to easily adjust settings and monitor performance, ensuring optimal operation over time.

In summary, Goodman Manufacturing's ARUF, ASPF, ADPF, and ATUF air handling units showcase cutting-edge technologies, robust construction, and energy-efficient designs. Each series offers unique features tailored to meet the diverse needs of customers, ensuring enhanced comfort and cost savings in residential and commercial environments. With a commitment to quality and innovation, Goodman continues to be a leader in the HVAC market.