SPLIT SYSTEM HEATING PERFORMANCE
EXPANDED PERFORMANCE DATA
MODEL: GSH140181A* / CA*F3131B6A*+TXV / |
|
|
|
|
|
|
| HEATING OPERATION | |||||||||||
|
|
|
|
|
|
|
| Outdoor Ambient Temperature |
|
|
|
|
|
|
|
| |||
|
| 65 | 60 | 55 | 50 | 47 | 45 | 40 | 35 | 30 | 25 | 20 | 17 | 15 | 10 | 5 | 0 | ||
| MBh | 22.6 | 21.4 | 20.2 | 18.8 | 18.0 | 17.4 | 16.2 | 14.9 | 13.6 | 12.5 | 11.5 | 10.9 | 10.5 | 9.4 | 8.3 | 7.3 | 6.2 | 5.1 |
| Delta T | 34.9 | 33.1 | 31.1 | 29.1 | 27.8 | 26.9 | 25.0 | 23.1 | 20.9 | 19.3 | 17.8 | 16.8 | 16.2 | 14.5 | 12.9 | 11.2 | 9.6 | 7.8 |
| KW | 1.56 | 1.53 | 1.50 | 1.47 | 1.46 | 1.44 | 1.41 | 1.38 | 1.38 | 1.35 | 1.32 | 1.30 | 1.28 | 1.25 | 1.22 | 1.19 | 1.16 | 1.13 |
| AMPS | 7.1 | 6.5 | 6.1 | 5.8 | 5.6 | 5.5 | 5.2 | 4.9 | 4.7 | 4.5 | 4.3 | 4.2 | 4.1 | 3.9 | 3.7 | 3.5 | 3.2 | 2.9 |
| COP | 4.23 | 4.09 | 3.93 | 3.75 | 3.62 | 3.54 | 3.36 | 3.16 | 2.88 | 2.72 | 2.56 | 2.45 | 2.39 | 2.19 | 1.99 | 1.78 | 1.56 | 1.31 |
| EER | 14.5 | 14.0 | 13.4 | 12.8 | 12.4 | 12.1 | 11.5 | 10.8 | 9.8 | 9.3 | 8.8 | 8.4 | 8.2 | 7.5 | 6.8 | 6.1 | 5.3 | 4.5 |
| HI PR | 248 | 237 | 228 | 218 | 213 | 209 | 201 | 193 | 185 | 176 | 169 | 165 | 162 | 156 | 150 | 144 | 139 | 134 |
| LO PR | 82 | 76 | 71 | 66 | 62 | 60 | 55 | 49 | 44 | 39 | 35 | 32 | 31 | 26 | 23 | 19 | 17 | 13 |
Above information is for nominal CFM and 70 degree indoor dry bulb.
MODEL: GSH140241A* / CA*F3636B6A*+TXV / MBR800**1 |
|
|
|
|
|
|
| HEATING OPERATION | |||||||||||
|
|
|
|
|
|
|
| Outdoor Ambient Temperature |
|
|
|
|
|
|
|
| |||
|
| 65 | 60 | 55 | 50 | 47 | 45 | 40 | 35 | 30 | 25 | 20 | 17 | 15 | 10 | 5 |
| ||
| MBh | 30.2 | 28.6 | 26.9 | 25.1 | 24.0 | 23.3 | 21.6 | 19.9 | 18.8 | 17.3 | 15.9 | 15.1 | 14.5 | 13.0 | 11.5 | 10.1 | 8.6 | 7.0 |
| Delta T | 32.9 | 31.1 | 29.3 | 27.4 | 26.1 | 25.3 | 23.5 | 21.7 | 20.4 | 18.9 | 17.4 | 16.4 | 15.8 | 14.2 | 12.6 | 11.0 | 9.4 | 7.7 |
| KW | 2.06 | 2.02 | 1.98 | 1.94 | 1.92 | 1.90 | 1.86 | 1.83 | 1.89 | 1.85 | 1.81 | 1.78 | 1.77 | 1.73 | 1.68 | 1.64 | 1.60 | 1.56 |
| AMPS | 7.9 | 7.6 | 7.5 | 7.3 | 7.2 | 7.2 | 7.1 | 7.0 | 6.9 | 6.8 | 6.7 | 6.7 | 6.6 | 6.5 | 6.4 | 6.4 | 6.2 | 6.1 |
| COP | 4.30 | 4.14 | 3.98 | 3.79 | 3.66 | 3.58 | 3.39 | 3.19 | 2.91 | 2.74 | 2.58 | 2.47 | 2.40 | 2.21 | 2.00 | 1.79 | 1.57 | 1.32 |
| EER | 14.7 | 14.2 | 13.6 | 13.0 | 12.5 | 12.2 | 11.6 | 10.9 | 9.9 | 9.4 | 8.8 | 8.4 | 8.2 | 7.5 | 6.8 | 6.1 | 5.4 | 4.5 |
| HI PR | 227 | 218 | 209 | 200 | 195 | 192 | 184 | 177 | 169 | 162 | 155 | 152 | 149 | 143 | 138 | 132 | 127 | 123 |
| LO PR | 80 | 74 | 70 | 64 | 61 | 58 | 54 | 48 | 43 | 38 | 34 | 31 | 30 | 26 | 22 | 19 | 16 | 13 |
Above information is for nominal CFM and 70 degree indoor dry bulb.
MODEL: GSH140301A* / CA*F3636B6A* +TXV / |
|
|
|
|
|
|
| HEATING OPERATION | |||||||||||
|
|
|
|
|
|
|
| Outdoor Ambient Temperature |
|
|
|
|
|
|
|
| |||
|
| 65 | 60 | 55 | 50 | 47 | 45 | 40 | 35 | 30 | 25 | 20 | 17 | 15 | 10 | 5 |
| ||
| MBh | 34.7 | 32.8 | 30.9 | 28.9 | 27.6 | 26.7 | 24.8 | 22.9 | 20.9 | 19.3 | 17.8 | 16.8 | 16.2 | 14.5 | 12.9 | 11.2 | 9.6 | 7.8 |
| Delta T | 29.8 | 28.2 | 26.5 | 24.8 | 23.7 | 22.9 | 21.3 | 19.6 | 18.0 | 16.6 | 15.3 | 14.4 | 13.9 | 12.4 | 11.0 | 9.6 | 8.2 | 6.7 |
| KW | 2.24 | 2.20 | 2.16 | 2.12 | 2.09 | 2.08 | 2.04 | 2.00 | 2.06 | 2.02 | 1.98 | 1.95 | 1.93 | 1.89 | 1.85 | 1.80 | 1.76 | 1.72 |
| AMPS | 9.6 | 8.9 | 8.4 | 7.9 | 7.6 | 7.5 | 7.1 | 6.7 | 6.4 | 6.2 | 5.9 | 5.7 | 5.7 | 5.4 | 5.0 | 4.8 | 4.4 | 4.0 |
| COP | 4.53 | 4.37 | 4.19 | 4.00 | 3.86 | 3.77 | 3.57 | 3.36 | 2.97 | 2.80 | 2.63 | 2.52 | 2.45 | 2.25 | 2.04 | 1.82 | 1.59 | 1.34 |
| EER | 15.5 | 14.9 | 14.3 | 13.7 | 13.2 | 12.9 | 12.2 | 11.5 | 10.1 | 9.6 | 9.0 | 8.6 | 8.4 | 7.7 | 7.0 | 6.2 | 5.4 | 4.6 |
| HI PR | 216 | 208 | 200 | 191 | 186 | 183 | 176 | 169 | 162 | 154 | 148 | 145 | 142 | 137 | 131 | 126 | 121 | 117 |
| LO PR | 80 | 74 | 69 | 64 | 60 | 58 | 53 | 47 | 43 | 38 | 34 | 31 | 30 | 25 | 22 | 19 | 16 | 13 |
Above information is for nominal CFM and 70 degree indoor dry bulb.
MODEL: GSH140361A* / CA*F4860C6A* +TXV / |
|
|
|
|
|
|
| HEATING OPERATION | |||||||||||
|
|
|
|
|
|
|
| Outdoor Ambient Temperature |
|
|
|
|
|
|
|
| |||
|
| 65 | 60 | 55 | 50 | 47 | 45 | 40 | 35 | 30 | 25 | 20 | 17 | 15 | 10 | 5 |
| ||
| MBh | 43.5 | 41.2 | 38.8 | 36.2 | 34.6 | 33.5 | 31.1 | 28.7 | 26.9 | 24.9 | 22.9 | 21.6 | 20.8 | 18.7 | 16.6 | 14.4 | 12.3 | 10.1 |
| Delta T | 37.8 | 35.8 | 33.7 | 31.5 | 30.1 | 29.1 | 27.1 | 25.0 | 23.4 | 21.6 | 19.9 | 18.8 | 18.1 | 16.2 | 14.4 | 12.6 | 10.7 | 8.8 |
| KW | 2.91 | 2.86 | 2.80 | 2.75 | 2.72 | 2.69 | 2.64 | 2.59 | 2.64 | 2.58 | 2.53 | 2.50 | 2.47 | 2.41 | 2.36 | 2.30 | 2.24 | 2.19 |
| AMPS | 13.1 | 12.2 | 11.4 | 10.8 | 10.4 | 10.2 | 9.7 | 9.2 | 8.8 | 8.5 | 8.1 | 7.9 | 7.8 | 7.4 | 7.0 | 6.6 | 6.1 | 5.6 |
| COP | 4.37 | 4.22 | 4.04 | 3.86 | 3.73 | 3.64 | 3.45 | 3.25 | 2.98 | 2.82 | 2.65 | 2.54 | 2.46 | 2.26 | 2.06 | 1.84 | 1.61 | 1.35 |
| EER | 14.9 | 14.4 | 13.8 | 13.2 | 12.7 | 12.4 | 11.8 | 11.1 | 10.2 | 9.6 | 9.1 | 8.7 | 8.4 | 7.7 | 7.0 | 6.3 | 5.5 | 4.6 |
| HI PR | 229 | 219 | 211 | 202 | 197 | 193 | 186 | 178 | 171 | 163 | 157 | 153 | 150 | 144 | 139 | 133 | 128 | 124 |
| LO PR | 83 | 77 | 72 | 66 | 63 | 60 | 55 | 49 | 44 | 40 | 35 | 32 | 31 | 26 | 23 | 19 | 17 | 13 |
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
High pressure is measured at the suction service valve ( the larger valve). Low pressure is measured at the gauge port connection.
AMPS = Outdoor unit amps (comp.+fan) KW = Total system power