Goodman Mfg IO-101G manual LINE CHARGE ALLOWANCE R-22oz./ft, Oil Charge Adjustment

Models: IO-101G

1 8
Download 8 pages 39.68 Kb
Page 6
Image 6
LINE CHARGE ALLOWANCE (R-22) (oz./ft.)

SPECIAL NOTE: Systems with MORE than 15’ of interconnecting tubing, please refer to Table 5 for line charge allowance per foot of tubing.

LINE CHARGE ALLOWANCE (R-22) (oz./ft.)

LINE

LIQUID

SUCTION

O. D. (IN)

LINE

LINE

 

 

 

1/4

0.22

 

3/8

0.58

 

1/2

1.14

 

5/8

1.86

0.04

3/4

 

0.06

7/8

 

0.08

1 1/8

 

0.15

1 3/8

 

0.22

TABLE 5

NOTE: System with over 50’ separation between condensing unit and evaporator may require oil charge adjustment.

OIL CHARGE ADJUSTMENT

UNIT MODEL

ADDITIONAL OIL CHARGE PER EACH

(TONS)

ADDITIONAL 10' OF LINE (OZ.)*

1 - 1

1/2

0.25

2 -

5

0.5

*Use either Texaco WF-32 (formerly cappella B)

or Suniso 3G-S oil

TABLE 6

IO-101G

6

06/04

 

Page 6