de-energized (heating) position. After giving the unit time to settle out, make sure the unit is supplying heated air.

12.If the outdoor ambient is above 80°F, the unit may trip on its high pressure cut out when on heating. The compressor should stop. The heating cycle must be thoroughly checked, so postpone the test to another day when conditions are more suitable but-DO NOT FAIL TO TEST.

If the outdoor ambient is low and the unit operates properly on the heating cycle, you may check the pressure cutout operation by blocking off the indoor return air until the unit trips.

13.If unit operates properly in the heating cycle, raise the temperature setting until the heating second stage makes contact. Supplemental resistance heat, if installed should now come on. Make sure it operates properly.

NOTE: If outdoor thermostats are installed the outdoor ambient must be below the set point of these thermostats for the heaters to operate. It may be necessary to jumper these thermostats to check heater operation if outdoor ambient is mild.

14.For thermostats with emergency heat switch, return to step 11. The emergency heat switch is located at the bottom of the thermostat. Move the switch to emergency heat. The heat pump will stop, the blower will continue to run, all heaters will come on and the thermostat emergency heat light will come on.

15.If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at least one defrost cycle to make sure the unit defrosts completely.

FINAL SYSTEM CHECKS

16.Check to see if all supply and return air grilles are adjusted and the air distribution system is balanced for the best compromise between heating and cooling.

17.Check for air leaks in the ductwork. See Sections on

Air Flow Adjustments.

18.Make sure the unit is free of “rattles”, and the tubing in the unit is free from excessive vibration. Also make sure tubes or lines are not rubbing against each other or sheet metal surfaces or edges. If so, correct the trouble.

19.Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use.

20.Be sure the Owner is instructed on the unit operation, filter, servicing, correct thermostat operation, etc.

REFRIGERATION PERFORMANCE CHECK

Under normal summertime (full load) operating conditions, superheat should be between 8°F and 12°F and sub-cooling measured at the condenser outlet should be 15°F (nominal). A 25°F to 35°F temperature difference should exist between the entering condenser air and the temperature correspond- ing to the compressor saturated discharge pressure. Check

that compressor RLA corresponds to values shown in Ap- pendix C. RLA draw can be much lower than values listed at low load conditions and low ambient condensing tempera- tures. Values in Appendix C can slightly exceed at high load conditions and high ambient condensing temperatures.

HEAT PUMP OPERATION

COOLING CYCLE

When the heat pump is in the cooling cycle, it operates ex- actly as a Summer Air Conditioner unit. In this mode, all the charts and data for service that apply to summer air condi- tioning apply to the heat pump. Most apply on the heating cycle except that “condenser” becomes “evaporator”, “evapo- rator” becomes “condenser”, “cooling” becomes “heating”.

HEATING CYCLE

The heat pump operates in the heating cycle by redirecting refrigerant flow through the refrigerant circuit external to the compressor. This is accomplished with through the reversing valve. Hot discharge vapor from the compressor is directed to the indoor coil (evaporator on the cooling cycle) where the heat is removed, and the vapor condenses to liquid. It then goes through the expansion device to the outdoor coil (con- denser on the cooling cycle) where the liquid is evaporated, and the vapor goes to the compressor.

When the solenoid valve coil is operated either from heating to cooling or vice versa, the piston in the reversing valve to the low pressure (high pressure) reverse positions in the re- versing valve.

The following figures show a schematic of a heat pump on the cooling cycle and the heating cycle. In addition to a re- versing valve, a heat pump is equipped with an expansion device and check valve for the indoor coil, and similar equip- ment for the outdoor coil. It is also provided with a defrost control system.

The expansion devices are flowrator distributors and perform the same function on the heating cycle as on the cooling cycle. The flowrator distributors also act as check valves to allow for the reverse of refrigerant flow.

13

Page 13
Image 13
Goodman Mfg IO-354B installation instructions Heat Pump Operation, Air Flow Adjustments

IO-354B specifications

The Goodman Mfg IO-354B is a high-efficiency, residential air conditioning unit known for its robust performance and reliability. As a part of Goodman’s commitment to providing affordable and efficient HVAC solutions, the IO-354B stands out with its advanced features, durable construction, and user-friendly technologies.

One of the primary highlights of the IO-354B is its impressive cooling capacity, making it a perfect choice for medium to large-sized homes. With a cooling capacity of 3.5 tons, this unit efficiently maintains comfortable indoor temperatures even during the hottest summer days. It operates quietly, ensuring that homeowners can enjoy a peaceful environment without the disruption of loud mechanical noises.

The IO-354B incorporates advanced multi-speed fan technology, which not only enhances air circulation but also promotes energy efficiency. This feature allows the system to adjust its speed based on current cooling needs, reducing energy consumption while ensuring optimal comfort. This makes the unit not only cost-effective but also environmentally friendly, as it helps to lower the carbon footprint of the household.

Efficiency is a hallmark of the IO-354B, boasting a high SEER rating. A higher Seasonal Energy Efficiency Ratio (SEER) translates to better energy savings; thus, reducing overall utility bills. This efficiency is further enhanced by the unit’s use of eco-friendly refrigerants, contributing to a greener solution for air conditioning needs.

Durability is another critical characteristic of the Goodman IO-354B. Constructed with a heavy-duty, galvanized steel cabinet, it is built to withstand even the toughest weather conditions. Additionally, the unit features a high-performance scroll compressor, known for its longevity and fewer moving parts, which results in a more reliable operation over time.

Goodman also places a strong emphasis on ease of maintenance with the IO-354B. Its user-friendly design includes removable panels that facilitate access for routine service and maintenance, ensuring that homeowners can keep their systems in optimal condition without hassle.

In summary, the Goodman Mfg IO-354B combines high efficiency, durability, and innovative technology to deliver comfort and affordability. Whether seeking to cool down a new home or replace an aging unit, the IO-354B is an excellent choice for those prioritizing performance and energy savings in their HVAC system. With a rich history in the industry, Goodman continues to be a trusted name in heating and air conditioning, and the IO-354B exemplifies this commitment to quality and innovation.