Goodman Mfg IO-354B Appendix A Blower Performance Tables Belt Drive, Standard Down Shot

Models: IO-354B

1 27
Download 27 pages 26.57 Kb
Page 21
Image 21

APPENDIX A BLOWER PERFORMANCE TABLES

BELT DRIVE

STANDARD DOWN SHOT

CPC/H036 STANDARD BELT DRIVE DOWN SHOT

ESP, In

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

1

 

2

 

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

 

 

 

 

 

 

 

 

 

 

 

 

 

1424

 

0.30

1239

 

0.23

0.4

 

 

 

 

 

 

 

1520

 

0.39

1292

 

0.29

1073

 

0.22

779

 

0.14

0.6

 

 

 

 

1439

 

0.40

1192

 

0.30

944

 

0.21

619

 

0.12

 

 

 

0.8

 

1350

 

0.42

1101

 

0.31

864

 

0.22

 

 

 

 

 

 

 

 

 

1.0

 

1028

 

0.31

729

 

0.21

 

 

 

 

 

 

 

 

 

 

 

 

1.2

 

675

 

0.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPC/H048 STANDARD BELT DRIVE DOWN SHOT

ESP, In

 

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

1

 

 

2

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

 

 

 

 

 

 

 

 

 

 

2129

 

0.64

1795

 

0.47

1550

 

0.35

0.4

 

 

 

 

 

 

 

1994

 

0.65

1701

 

0.49

1433

 

0.36

1163

 

0.22

0.6

 

 

 

 

1905

 

0.67

1606

 

0.50

1326

 

0.36

1025

 

0.22

 

 

 

0.8

 

1808

 

0.69

1565

 

0.54

1216

 

0.36

 

 

 

 

 

 

 

 

 

1.0

 

1473

 

0.55

1137

 

0.32

 

 

 

 

 

 

 

 

 

 

 

 

1.2

 

1103

 

0.41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPC/H060 STANDARD BELT DRIVE DOWN SHOT

ESP, In

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

1

 

2

 

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

 

 

 

 

 

 

 

2579

 

1.01

2368

 

0.85

2175

 

0.691

1961

 

0.55

0.4

 

 

 

 

2513

 

1.05

2318

 

0.89

2089

 

0.73

1906

 

0.59

1666

 

0.44

0.6

 

2514

 

1.14

2276

 

0.94

2045

 

0.77

1797

 

0.60

1604

 

0.47

 

 

 

0.8

 

2261

 

1.01

2017

 

0.82

1760

 

0.63

 

 

 

 

 

 

 

 

 

1.0

 

1989

 

0.87

1730

 

0.68

 

 

 

 

 

 

 

 

 

 

 

 

1.2

 

1695

 

0.72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CPC/H072 STANDARD BELT DRIVE DOWN SHOT

ESP, In

 

 

 

 

 

 

 

 

 

TURNS OPEN

 

 

 

 

 

 

 

 

0

 

 

1

 

2

3

 

4

 

 

5

H2O

 

 

 

 

 

 

 

 

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

CFM

 

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

 

 

 

 

 

 

 

2771

 

1.27

2567

 

1.05

2421

 

0.88

2220

 

0.71

0.4

 

 

 

 

2753

 

1.38

2573

 

1.15

2382

 

0.95

2186

 

0.77

1980

 

0.61

0.6

 

2655

 

1.42

2548

 

1.24

2360

 

1.02

2119

 

0.81

1934

 

0.65

 

 

 

0.8

 

2470

 

1.30

2331

 

1.11

2111

 

0.89

1868

 

0.69

 

 

 

 

 

 

1.0

 

2296

 

1.18

2078

 

0.96

1840

 

0.75

 

 

 

 

 

 

 

 

 

1.2

 

2040

 

1.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.

21

Page 21
Image 21
Goodman Mfg IO-354B installation instructions Appendix A Blower Performance Tables Belt Drive, Standard Down Shot