Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower
than supply air end.
To assist in determining rigging requirements, unit weights are shown as follows:
A |
| C |
|
| RETURN |
Y | CONDENSER |
|
|
| |
| COIL | EVAPORATOR COIL |
|
| |
|
| CG |
|
| SUPPLY |
B | COMPRESSOR | D |
| ||
| X |
|
CORNER & CENTER OF GRAVITY LOCATIONS
Model | X | Y | Shipping Weight | Operating Weight |
| Corner Weights ( lbs ) |
| ||
(in) | (in) | (lbs) | (lbs) | A | B | C |
| D | |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
CPC036* | 35 | 27 | 525 | 500 | 115 | 150 | 105 |
| 130 |
|
|
|
|
|
|
|
|
|
|
CPC048* | 35 | 27 | 560 | 535 | 125 | 160 | 110 |
| 140 |
|
|
|
|
|
|
|
|
|
|
CPC060* | 35 | 27 | 605 | 580 | 135 | 170 | 120 |
| 155 |
|
|
|
|
|
|
|
|
|
|
CPC072* | 35 | 27 | 665 | 640 | 150 | 190 | 130 |
| 170 |
|
|
|
|
|
|
|
|
|
|
CPH036* | 34 | 28 | 605 | 580 | 130 | 180 | 110 |
| 155 |
|
|
|
|
|
|
|
|
|
|
CPH048* | 34 | 28 | 610 | 585 | 135 | 185 | 115 |
| 155 |
|
|
|
|
|
|
|
|
|
|
CPH060* | 34 | 28 | 615 | 590 | 135 | 185 | 115 |
| 160 |
|
|
|
|
|
|
|
|
|
|
CPH072* | 34 | 28 | 675 | 650 | 145 | 205 | 125 |
| 175 |
|
|
|
|
|
|
|
|
|
|
* Weights shown are belt drive with no accessories.
7