APPENDIX A BLOWER PERFORMANCE TABLES
DIRECT DRIVE
STANDARD CPC/H060 HORIZONTAL
CPC/H060 DIRECT DRIVE HORIZONTAL
SPEED | EXTERNAL STATIC | STANDARD |
|
|
| |
PRESSURE (ESP) | AMPS | WATTS | RPM | |||
TAP | CFM | |||||
in w.c. |
|
|
| |||
|
|
|
|
| ||
|
|
|
|
|
| |
| 0.10 | 1355 | 1.57 | 174 | 599 | |
| 0.20 | 1281 | 1.66 | 182 | 651 | |
| 0.30 | 1235 | 1.76 | 196 | 693 | |
| 0.40 | 1168 | 1.81 | 202 | 726 | |
T1 | 0.50 | 1118 | 1.94 | 218 | 775 | |
| 0.60 | 1049 | 2.03 | 232 | 819 | |
| 0.70 | 982 | 2.10 | 240 | 858 | |
| 0.80 | 922 | 2.14 | 246 | 885 | |
| 0.90 | 871 | 2.25 | 260 | 927 | |
| 0.10 | 1544 | 2.04 | 234 | 660 | |
| 0.20 | 1490 | 2.17 | 250 | 704 | |
| 0.30 | 1427 | 2.25 | 260 | 742 | |
| 0.40 | 1370 | 2.35 | 276 | 781 | |
T2 | 0.50 | 1319 | 2.42 | 282 | 809 | |
| 0.60 | 1274 | 2.52 | 296 | 849 | |
| 0.70 | 1210 | 2.62 | 316 | 891 | |
| 0.80 | 1137 | 2.73 | 326 | 935 | |
| 0.90 | 1106 | 2.77 | 336 | 957 | |
| 0.10 | 2099 | 4.13 | 516 | 825 | |
| 0.20 | 2068 | 4.25 | 536 | 852 | |
| 0.30 | 2029 | 4.37 | 552 | 885 | |
T3 | 0.40 | 1971 | 4.48 | 568 | 913 | |
0.50 | 1911 | 4.61 | 586 | 950 | ||
| 0.60 | 1876 | 4.73 | 604 | 973 | |
| 0.70 | 1821 | 4.86 | 622 | 1012 | |
| 0.80 | 1792 | 4.91 | 630 | 1028 | |
| 0.90 | 1740 | 5.03 | 648 | 1067 | |
| 0.10 | 2233 | 4.76 | 608 | 863 | |
| 0.20 | 2168 | 4.91 | 628 | 896 | |
| 0.30 | 2125 | 5.02 | 640 | 924 | |
| 0.40 | 2070 | 5.14 | 660 | 951 | |
T4 | 0.50 | 2050 | 5.27 | 678 | 979 | |
| 0.60 | 1980 | 5.41 | 696 | 1012 | |
| 0.70 | 1954 | 5.47 | 704 | 1034 | |
| 0.80 | 1893 | 5.60 | 724 | 1067 | |
| 0.90 | 1852 | 5.70 | 736 | 1089 | |
| 0.10 | 2322 | 5.44 | 710 | 904 | |
| 0.20 | 2294 | 5.55 | 726 | 934 | |
| 0.30 | 2254 | 5.68 | 742 | 958 | |
| 0.40 | 2201 | 5.80 | 766 | 990 | |
T5 | 0.50 | 2147 | 5.93 | 782 | 1017 | |
| 0.60 | 2117 | 6.01 | 788 | 1039 | |
| 0.70 | 2081 | 6.12 | 808 | 1060 | |
| 0.80 | 2017 | 6.22 | 822 | 1094 | |
| 0.90 | 1932 | 6.10 | 804 | 1111 |
NOTES:
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.
20